|
RXYQ8U7Y1B |
RXYQ10U7Y1B |
RXYQ12U7Y1B |
RXYQ14U7Y1B |
RXYQ16U7Y1B |
RXYQ18U7Y1B |
RXYQ20U7Y1B |
RXYQ22U7Y1B |
RXYQ24U7Y1B |
RXYQ26U7Y1B |
RXYQ28U7Y1B |
RXYQ30U7Y1B |
RXYQ32U7Y1B |
RXYQ34U7Y1B |
RXYQ36U7Y1B |
RXYQ38U7Y1B |
RXYQ40U7Y1B |
RXYQ42U7Y1B |
RXYQ44U7Y1B |
RXYQ46U7Y1B |
RXYQ48U7Y1B |
RXYQ50U7Y1B |
RXYQ52U7Y1B |
RXYQ54U7Y1B |
System |
Outdoor unit module 1 |
|
|
|
|
|
|
|
RXYQ10U |
RXYQ8U |
RXYQ12U |
RXYQ12U |
RXYQ12U |
RXYQ16U |
RXYQ16U |
RXYQ16U |
RXYQ8U |
RXYQ10U |
RXYQ10U |
RXYQ12U |
RXYQ14U |
RXYQ16U |
RXYQ16U |
RXYQ16U |
RXYQ18U |
|
Outdoor unit module 2 |
|
|
|
|
|
|
|
RXYQ12U |
RXYQ16U |
RXYQ14U |
RXYQ16U |
RXYQ18U |
RXYQ16U |
RXYQ18U |
RXYQ20U |
RXYQ10U |
RXYQ12U |
RXYQ16U |
RXYQ16U |
RXYQ16U |
RXYQ16U |
RXYQ16U |
RXYQ18U |
RXYQ18U |
|
Outdoor unit module 3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RXYQ20U |
RXYQ18U |
RXYQ16U |
RXYQ16U |
RXYQ16U |
RXYQ16U |
RXYQ18U |
RXYQ18U |
RXYQ18U |
Recommended combination |
4 x FXFQ50AVEB |
4 x FXFQ63AVEB |
6 x FXFQ50AVEB |
1 x FXFQ50AVEB + 5 x FXFQ63AVEB |
4 x FXFQ63AVEB + 2 x FXFQ80AVEB |
3 x FXFQ50AVEB + 5 x FXFQ63AVEB |
2 x FXFQ50AVEB + 6 x FXFQ63AVEB |
6 x FXFQ50AVEB + 4 x FXFQ63AVEB |
4 x FXFQ50AVEB + 4 x FXFQ63AVEB + 2 x FXFQ80AVEB |
7 x FXFQ50AVEB + 5 x FXFQ63AVEB |
6 x FXFQ50AVEB + 4 x FXFQ63AVEB + 2 x FXFQ80AVEB |
9 x FXFQ50AVEB + 5 x FXFQ63AVEB |
8 x FXFQ63AVEB + 4 x FXFQ80AVEB |
3 x FXFQ50AVEB + 9 x FXFQ63AVEB + 2 x FXFQ80AVEB |
2 x FXFQ50AVEB + 10 x FXFQ63AVEB + 2 x FXFQ80AVEB |
6 x FXFQ50AVEB + 10 x FXFQ63AVEB |
9 x FXFQ50AVEB + 9 x FXFQ63AVEB |
12 x FXFQ63AVEB + 4 x FXFQ80AVEB |
6 x FXFQ50AVEB + 8 x FXFQ63AVEB + 4 x FXFQ80AVEB |
1 x FXFQ50AVEB + 13 x FXFQ63AVEB + 4 x FXFQ80AVEB |
12 x FXFQ63AVEB + 6 x FXFQ80AVEB |
3 x FXFQ50AVEB + 13 x FXFQ63AVEB + 4 x FXFQ80AVEB |
6 x FXFQ50AVEB + 14 x FXFQ63AVEB + 2 x FXFQ80AVEB |
9 x FXFQ50AVEB + 15 x FXFQ63AVEB |
Recommended combination 2 |
4 x FXSQ50A2VEB |
4 x FXSQ63A2VEB |
6 x FXSQ50A2VEB |
1 x FXSQ50A2VEB + 5 x FXSQ63A2VEB |
4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB |
3 x FXSQ50A2VEB + 5 x FXSQ63A2VEB |
2 x FXSQ50A2VEB + 6 x FXSQ63A2VEB |
6 x FXSQ50A2VEB + 4 x FXSQ63A2VEB |
4 x FXSQ50A2VEB + 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB |
7 x FXSQ50A2VEB + 5 x FXSQ63A2VEB |
6 x FXSQ50A2VEB + 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB |
9 x FXSQ50A2VEB + 5 x FXSQ63A2VEB |
8 x FXSQ63A2VEB + 4 x FXSQ80A2VEB |
3 x FXSQ50A2VEB + 9 x FXSQ63A2VEB + 2 x FXSQ80A2VEB |
2 x FXSQ50A2VEB + 10 x FXSQ63A2VEB + 2 x FXSQ80A2VEB |
6 x FXSQ50A2VEB + 10 x FXSQ63A2VEB |
9 x FXSQ50A2VEB + 9 x FXSQ63A2VEB |
12 x FXSQ63A2VEB + 4 x FXSQ80A2VEB |
6 x FXSQ50A2VEB + 8 x FXSQ63A2VEB + 4 x FXSQ80A2VEB |
1 x FXSQ50A2VEB + 13 x FXSQ63A2VEB + 4 x FXSQ80A2VEB |
12 x FXSQ63A2VEB + 6 x FXSQ80A2VEB |
3 x FXSQ50A2VEB + 13 x FXSQ63A2VEB + 4 x FXSQ80A2VEB |
6 x FXSQ50A2VEB + 14 x FXSQ63A2VEB + 2 x FXSQ80A2VEB |
9 x FXSQ50A2VEB + 15 x FXSQ63A2VEB |
Recommended combination 3 |
4 x FXMQ50P7VEB |
4 x FXMQ63P7VEB |
6 x FXMQ50P7VEB |
1 x FXMQ50P7VEB + 5 x FXMQ63P7VEB |
4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB |
3 x FXMQ50P7VEB + 5 x FXMQ63P7VEB |
2 x FXMQ50P7VEB + 6 x FXMQ63P7VEB |
6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB |
4 x FXMQ50P7VEB + 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB |
7 x FXMQ50P7VEB + 5 x FXMQ63P7VEB |
6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB |
9 x FXMQ50P7VEB + 5 x FXMQ63P7VEB |
8 x FXMQ63P7VEB + 4 x FXMQ80P7VEB |
3 x FXMQ50P7VEB + 9 x FXMQ63P7VEB + 2 x FXMQ80P7VEB |
2 x FXMQ50P7VEB + 10 x FXMQ63P7VEB + 2 x FXMQ80P7VEB |
6 x FXMQ50P7VEB + 10 x FXMQ63P7VEB |
9 x FXMQ50P7VEB + 9 x FXMQ63P7VEB |
12 x FXMQ63P7VEB + 4 x FXMQ80P7VEB |
6 x FXMQ50P7VEB + 8 x FXMQ63P7VEB + 4 x FXMQ80P7VEB |
1 x FXMQ50P7VEB + 13 x FXMQ63P7VEB + 4 x FXMQ80P7VEB |
12 x FXMQ63P7VEB + 6 x FXMQ80P7VEB |
3 x FXMQ50P7VEB + 13 x FXMQ63P7VEB + 4 x FXMQ80P7VEB |
6 x FXMQ50P7VEB + 14 x FXMQ63P7VEB + 2 x FXMQ80P7VEB |
9 x FXMQ50P7VEB + 15 x FXMQ63P7VEB |
Cooling capacity |
Prated,c |
kW |
22.4 (1) |
28.0 (1) |
33.5 (1) |
40.0 (1) |
45.0 (1) |
50.4 (1) |
52.0 (1) |
61.5 (1) |
67.4 (1) |
73.5 (1) |
78.5 (1) |
83.9 (1) |
90.0 (1) |
95.4 (1) |
97.0 (1) |
102.4 (1) |
111.9 (1) |
118.0 (1) |
123.5 (1) |
130.0 (1) |
135.0 (1) |
140.4 (1) |
145.8 (1) |
151.2 (1) |
Heating capacity |
Prated,h |
kW |
22.4 (2) |
28.0 (2) |
33.5 (2) |
40.0 (2) |
45.0 (2) |
50.4 (2) |
56.0 (2) |
61.5 (2) |
67.4 (2) |
73.5 (2) |
78.5 (2) |
83.9 (2) |
90.0 (2) |
95.4 (2) |
101.0 (2) |
106.4 (2) |
111.9 (2) |
118.0 (2) |
123.5 (2) |
130.0 (2) |
135.0 (2) |
140.4 (2) |
145.8 (2) |
151.2 (2) |
|
Nom. |
6°CWB |
kW |
22.4 (2) |
28.0 (2) |
33.5 (2) |
40.0 (2) |
45.0 (2) |
50.4 (2) |
56.0 (2) |
61.5 (2) |
67.4 (2) |
73.5 (2) |
78.5 (2) |
83.9 (2) |
90.0 (2) |
95.4 (2) |
101.0 (2) |
106.4 (2) |
111.9 (2) |
118.0 (2) |
123.5 (2) |
130.0 (2) |
135.0 (2) |
140.4 (2) |
145.8 (2) |
151.2 (2) |
Power input - 50Hz |
Heating |
Nom. |
6°CWB |
kW |
5.40 (2) |
7.58 (2) |
9.65 (2) |
10.69 (2) |
12.54 (2) |
14.22 (2) |
17.47 (2) |
17.23 (2) |
17.94 (2) |
20.33 (2) |
22.19 (2) |
23.87 (2) |
25.08 (2) |
26.76 (2) |
30.02 (2) |
30.45 (2) |
31.45 (2) |
32.66 (2) |
34.73 (2) |
35.77 (2) |
37.62 (2) |
39.30 (2) |
40.98 (2) |
42.66 (2) |
COP at nom. capacity |
6°CWB |
kW/kW |
4.15 (2) |
3.69 (2) |
3.47 (2) |
3.74 (2) |
3.59 (2) |
3.54 (2) |
3.20 (2) |
3.57 (2) |
3.76 (2) |
3.61 (2) |
3.54 (2) |
3.51 (2) |
3.59 (2) |
3.56 (2) |
3.36 (2) |
3.49 (2) |
3.56 (2) |
3.61 (2) |
3.56 (2) |
3.63 (2) |
3.59 (2) |
3.57 (2) |
3.56 (2) |
3.54 (2) |
SCOP |
4.3 |
4.3 |
4.1 |
4.0 |
4.0 |
4.2 |
4.0 |
4.4 |
4.3 |
4.2 |
4.2 |
4.3 |
4.2 |
4.2 |
4.1 |
4.3 |
4.3 |
4.2 |
4.2 |
4.1 |
4.1 |
4.2 |
4.3 |
4.3 |
SCOP recommended combination 2 |
4.2 |
4.3 |
4.1 |
4.0 |
4.1 |
4.2 |
4.0 |
4.4 |
4.3 |
4.2 |
4.2 |
4.3 |
4.2 |
4.3 |
4.2 |
4.3 |
4.4 |
4.3 |
4.2 |
4.2 |
4.2 |
4.2 |
4.3 |
4.3 |
SCOP recommended combination 3 |
4.2 |
4.1 |
4.1 |
4.0 |
4.0 |
4.1 |
3.9 |
4.3 |
4.2 |
4.2 |
4.2 |
4.3 |
4.1 |
4.2 |
4.1 |
4.2 |
4.3 |
4.2 |
4.2 |
4.1 |
4.1 |
4.2 |
4.2 |
4.2 |
SEER |
7.6 |
6.8 |
6.3 |
6.3 |
6.0 |
6.0 |
5.9 |
6.9 |
6.8 |
6.7 |
6.5 |
6.5 |
6.4 |
6.4 |
6.3 |
6.9 |
6.7 |
6.6 |
6.5 |
6.4 |
6.4 |
6.4 |
6.4 |
6.4 |
SEER recommended combination 2 |
6.9 |
6.8 |
5.9 |
6.3 |
5.9 |
6.0 |
5.9 |
6.7 |
6.6 |
6.5 |
6.3 |
6.3 |
6.3 |
6.3 |
6.3 |
6.8 |
6.6 |
6.6 |
6.3 |
6.4 |
6.3 |
6.3 |
6.4 |
6.4 |
SEER recommended combination 3 |
7.5 |
6.8 |
6.2 |
6.2 |
5.8 |
6.0 |
5.9 |
6.9 |
6.7 |
6.6 |
6.4 |
6.5 |
6.2 |
6.3 |
6.3 |
6.9 |
6.7 |
6.5 |
6.3 |
6.3 |
6.2 |
6.3 |
6.4 |
6.4 |
ηs,c |
% |
302.4 |
267.6 |
247.8 |
250.7 |
236.5 |
238.3 |
233.7 |
274.5 |
269.9 |
264.2 |
257.8 |
256.8 |
251.7 |
253.3 |
250.8 |
272.4 |
263.5 |
261.2 |
255.9 |
254.9 |
251.7 |
252.8 |
253.7 |
254.1 |
ηs,c recommended combination 2 |
273.6 |
270.5 |
233.5 |
250.0 |
234.2 |
236.8 |
233.9 |
266.5 |
262.6 |
256.1 |
249.3 |
249.8 |
248.3 |
250.9 |
248.7 |
269.2 |
259.2 |
259.3 |
249.2 |
252.2 |
248.3 |
250.0 |
251.6 |
252.5 |
ηs,c recommended combination 3 |
295.2 |
267.1 |
246.3 |
246.7 |
230.4 |
238.2 |
233.1 |
273.3 |
265.3 |
261.1 |
253.1 |
256.1 |
244.2 |
249.8 |
247.2 |
272.2 |
263.2 |
255.4 |
250.1 |
248.3 |
244.2 |
248.0 |
251.5 |
253.9 |
ηs,h |
% |
167.9 |
168.2 |
161.4 |
155.4 |
157.8 |
163.1 |
156.6 |
171.2 |
167.0 |
164.6 |
166.0 |
169.8 |
163.1 |
166.2 |
162.4 |
167.5 |
170.0 |
165.5 |
164.5 |
162.0 |
162.8 |
165.2 |
167.2 |
169.4 |
ηs,h recommended combination 2 |
165.4 |
170.6 |
161.3 |
157.2 |
159.5 |
164.8 |
158.2 |
172.3 |
167.1 |
165.4 |
166.8 |
170.6 |
164.6 |
167.7 |
164.1 |
168.4 |
171.3 |
167.3 |
165.6 |
163.5 |
164.3 |
166.7 |
168.7 |
170.8 |
ηs,h recommended combination 3 |
165.6 |
162.0 |
160.6 |
155.7 |
156.8 |
159.6 |
153.4 |
170.2 |
165.5 |
164.5 |
165.0 |
167.0 |
161.9 |
164.2 |
159.9 |
164.8 |
167.8 |
164.4 |
163.5 |
161.3 |
161.7 |
163.2 |
164.4 |
166.0 |
Space cooling |
A Condition (35°C - 27/19) |
EERd |
|
3.0 |
2.3 |
2.4 |
2.6 |
2.1 |
1.9 |
1.9 |
2.6 |
2.5 |
2.6 |
2.3 |
2.1 |
2.3 |
2.1 |
2.1 |
2.4 |
2.2 |
2.3 |
2.3 |
2.4 |
2.3 |
2.1 |
2.0 |
1.9 |
|
|
Pdc |
kW |
22.4 |
28.0 |
33.5 |
40.0 |
45.0 |
50.4 |
52.0 |
61.5 |
67.4 |
73.5 |
78.5 |
83.9 |
90.0 |
95.4 |
97.0 |
102.4 |
111.9 |
118.0 |
123.5 |
130.0 |
135.0 |
140.4 |
145.8 |
151.2 |
|
B Condition (30°C - 27/19) |
EERd |
|
5.2 |
4.7 |
4.3 |
4.1 |
3.9 |
3.8 |
3.7 |
4.8 |
4.6 |
4.6 |
4.4 |
4.3 |
4.3 |
4.2 |
4.1 |
4.5 |
4.5 |
4.4 |
4.4 |
4.4 |
4.3 |
4.2 |
4.2 |
4.1 |
|
|
Pdc |
kW |
16.5 |
20.6 |
24.7 |
29.5 |
33.2 |
37.1 |
38.3 |
45.3 |
49.7 |
54.2 |
57.8 |
61.8 |
66.3 |
70.3 |
71.5 |
75.5 |
82.5 |
86.9 |
91.0 |
95.8 |
99.5 |
103.4 |
107.4 |
111.4 |
|
C Condition (25°C - 27/19) |
EERd |
|
9.5 |
8.3 |
7.7 |
7.8 |
7.7 |
7.5 |
7.3 |
8.5 |
8.6 |
8.2 |
8.1 |
8.2 |
8.1 |
8.1 |
7.9 |
8.5 |
8.3 |
8.2 |
8.1 |
8.1 |
8.1 |
8.1 |
8.1 |
8.1 |
|
|
Pdc |
kW |
10.6 |
13.3 |
15.9 |
18.9 |
21.3 |
23.9 |
24.6 |
29.1 |
31.9 |
34.8 |
37.2 |
39.7 |
42.6 |
45.2 |
45.9 |
48.5 |
53.0 |
55.9 |
58.5 |
61.6 |
64.0 |
66.5 |
69.1 |
71.6 |
|
D Condition (20°C - 27/19) |
EERd |
|
18.8 |
17.0 |
13.9 |
14.3 |
14.2 |
18.3 |
18.3 |
16.0 |
15.2 |
14.2 |
14.3 |
16.8 |
14.3 |
16.8 |
16.7 |
17.9 |
16.0 |
15.4 |
14.4 |
14.3 |
14.3 |
15.9 |
17.6 |
19.1 |
|
|
Pdc |
kW |
8.0 |
9.3 |
9.4 |
8.4 |
9.5 |
11.5 |
11.5 |
18.8 |
15.8 |
16.2 |
16.5 |
21.0 |
19.0 |
20.1 |
20.4 |
21.6 |
23.6 |
24.8 |
26.0 |
27.4 |
28.4 |
29.6 |
30.7 |
34.4 |
Space cooling recommended combination 2 |
A Condition (35°C - 27/19) |
EERd |
|
2.6 |
2.4 |
2.4 |
2.6 |
2.1 |
1.9 |
1.9 |
2.6 |
2.4 |
2.6 |
2.3 |
2.1 |
2.2 |
2.1 |
2.1 |
2.3 |
2.2 |
2.3 |
2.3 |
2.3 |
2.2 |
2.1 |
2.0 |
1.9 |
|
|
Pdc |
kW |
22.4 |
28.0 |
33.5 |
40.0 |
45.0 |
50.4 |
52.0 |
61.5 |
67.4 |
73.5 |
78.5 |
83.9 |
90.0 |
95.4 |
97.0 |
102.4 |
111.9 |
118.0 |
123.5 |
130.0 |
135.0 |
140.4 |
145.8 |
151.2 |
|
B Condition (30°C - 27/19) |
EERd |
|
4.9 |
4.7 |
4.0 |
4.1 |
3.8 |
3.7 |
3.6 |
4.6 |
4.5 |
4.4 |
4.3 |
4.2 |
4.2 |
4.2 |
4.1 |
4.5 |
4.4 |
4.4 |
4.3 |
4.3 |
4.2 |
4.2 |
4.1 |
4.1 |
|
|
Pdc |
kW |
16.5 |
20.6 |
24.7 |
29.5 |
33.2 |
37.1 |
38.3 |
45.3 |
49.7 |
54.1 |
57.8 |
61.8 |
66.3 |
70.3 |
71.5 |
75.4 |
82.4 |
86.9 |
91.0 |
95.8 |
99.5 |
103.5 |
107.4 |
111.4 |
|
C Condition (25°C - 27/19) |
EERd |
|
8.8 |
8.5 |
7.1 |
7.9 |
7.6 |
7.5 |
7.3 |
8.2 |
8.4 |
7.9 |
7.8 |
7.9 |
8.0 |
8.1 |
7.9 |
8.4 |
8.1 |
8.2 |
7.9 |
8.1 |
8.0 |
8.0 |
8.1 |
8.1 |
|
|
Pdc |
kW |
10.6 |
13.3 |
15.9 |
18.9 |
21.3 |
23.9 |
24.6 |
29.1 |
31.9 |
34.8 |
37.2 |
39.7 |
42.6 |
45.2 |
45.9 |
48.5 |
53.0 |
55.9 |
58.5 |
61.6 |
63.9 |
66.5 |
69.0 |
71.6 |
|
D Condition (20°C - 27/19) |
EERd |
|
15.1 |
17.2 |
13.1 |
14.0 |
14.0 |
18.1 |
18.9 |
15.6 |
14.7 |
13.6 |
13.8 |
16.1 |
14.0 |
16.5 |
16.5 |
17.8 |
15.9 |
15.3 |
14.0 |
14.0 |
14.0 |
15.6 |
17.4 |
18.9 |
|
|
Pdc |
kW |
8.8 |
9.3 |
9.1 |
8.4 |
9.5 |
11.4 |
10.9 |
18.4 |
15.4 |
15.7 |
16.5 |
20.5 |
18.9 |
20.1 |
20.4 |
21.6 |
23.6 |
24.8 |
26.0 |
27.4 |
28.4 |
29.6 |
30.7 |
34.1 |
Space cooling recommended combination 3 |
A Condition (35°C - 27/19) |
EERd |
|
3.0 |
2.3 |
2.4 |
2.6 |
2.1 |
1.9 |
1.9 |
2.5 |
2.5 |
2.5 |
2.3 |
2.1 |
2.2 |
2.1 |
2.1 |
2.4 |
2.2 |
2.3 |
2.3 |
2.3 |
2.2 |
2.1 |
2.0 |
1.9 |
|
|
Pdc |
kW |
22.4 |
28.0 |
33.5 |
40.0 |
45.0 |
50.4 |
52.0 |
61.5 |
67.4 |
73.5 |
78.5 |
83.9 |
90.0 |
95.4 |
97.0 |
102.4 |
111.9 |
118.0 |
123.5 |
130.0 |
135.0 |
140.4 |
145.8 |
151.2 |
|
B Condition (30°C - 27/19) |
EERd |
|
5.1 |
4.7 |
4.2 |
4.0 |
3.7 |
3.7 |
3.6 |
4.8 |
4.5 |
4.5 |
4.3 |
4.3 |
4.1 |
4.1 |
4.0 |
4.5 |
4.4 |
4.3 |
4.3 |
4.2 |
4.1 |
4.1 |
4.1 |
4.1 |
|
|
Pdc |
kW |
16.5 |
20.6 |
24.7 |
29.5 |
33.2 |
37.1 |
38.3 |
45.3 |
49.7 |
54.2 |
57.8 |
61.8 |
66.3 |
70.3 |
71.5 |
75.5 |
82.5 |
87.0 |
91.0 |
95.8 |
99.5 |
103.5 |
107.4 |
111.4 |
|
C Condition (25°C - 27/19) |
EERd |
|
9.6 |
8.4 |
7.7 |
7.7 |
7.4 |
7.6 |
7.3 |
8.5 |
8.4 |
8.1 |
8.0 |
8.2 |
7.8 |
8.0 |
7.8 |
8.5 |
8.4 |
8.0 |
7.9 |
7.9 |
7.8 |
7.9 |
8.0 |
8.2 |
|
|
Pdc |
kW |
10.6 |
13.3 |
15.9 |
19.0 |
21.3 |
23.9 |
24.6 |
29.1 |
31.9 |
34.8 |
37.2 |
39.7 |
42.6 |
45.2 |
45.9 |
48.5 |
53.0 |
55.9 |
58.5 |
61.6 |
63.9 |
66.5 |
69.1 |
71.6 |
|
D Condition (20°C - 27/19) |
EERd |
|
16.0 |
16.9 |
13.7 |
14.0 |
14.1 |
18.3 |
18.3 |
15.8 |
15.2 |
14.0 |
14.1 |
16.6 |
13.8 |
16.6 |
16.5 |
17.9 |
16.1 |
15.2 |
14.2 |
13.9 |
13.8 |
15.6 |
17.5 |
19.1 |
|
|
Pdc |
kW |
9.1 |
9.3 |
9.4 |
8.4 |
9.5 |
11.6 |
11.6 |
18.8 |
15.7 |
16.0 |
16.6 |
21.0 |
19.0 |
20.1 |
20.4 |
21.6 |
23.6 |
24.8 |
26.0 |
27.4 |
28.4 |
29.6 |
30.7 |
34.7 |
Space heating (Average climate) |
TBivalent |
COPd (declared COP) |
|
2.5 |
2.4 |
2.0 |
2.3 |
2.2 |
1.9 |
1.8 |
2.3 |
2.5 |
2.3 |
2.2 |
2.1 |
2.4 |
2.2 |
2.1 |
2.2 |
2.2 |
2.4 |
2.3 |
2.4 |
2.4 |
2.3 |
2.2 |
2.1 |
|
|
Pdh (declared heating cap) |
kW |
13.7 |
16.0 |
18.4 |
20.6 |
23.2 |
27.9 |
31.0 |
34.4 |
36.9 |
39.0 |
41.6 |
46.3 |
46.4 |
51.1 |
54.2 |
60.7 |
62.3 |
62.4 |
64.8 |
67.0 |
69.6 |
74.3 |
79.0 |
83.7 |
|
|
Tbiv (bivalent temperature) |
°C |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
|
TOL |
COPd (declared COP) |
|
2.5 |
2.4 |
2.0 |
2.3 |
2.2 |
1.9 |
1.8 |
2.3 |
2.5 |
2.3 |
2.2 |
2.1 |
2.4 |
2.2 |
2.1 |
2.2 |
2.2 |
2.4 |
2.3 |
2.4 |
2.4 |
2.3 |
2.2 |
2.1 |
|
|
Pdh (declared heating cap) |
kW |
13.7 |
16.0 |
18.4 |
20.6 |
23.2 |
27.9 |
31.0 |
34.4 |
36.9 |
39.0 |
41.6 |
46.3 |
46.4 |
51.1 |
54.2 |
60.7 |
62.3 |
62.4 |
64.8 |
67.0 |
69.6 |
74.3 |
79.0 |
83.7 |
|
|
Tol (temperature operating limit) |
°C |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
|
A Condition (-7°C) |
COPd (declared COP) |
|
2.7 |
2.6 |
2.4 |
2.6 |
2.6 |
2.4 |
2.1 |
2.6 |
2.8 |
2.6 |
2.6 |
2.6 |
2.7 |
2.6 |
2.5 |
2.5 |
2.6 |
2.7 |
2.7 |
2.7 |
2.7 |
2.7 |
2.6 |
2.6 |
|
|
Pdh (declared heating cap) |
kW |
12.1 |
14.2 |
16.3 |
18.2 |
20.5 |
24.7 |
27.4 |
30.4 |
32.6 |
34.5 |
36.8 |
41.0 |
41.0 |
45.2 |
47.9 |
53.7 |
55.1 |
55.2 |
57.3 |
59.3 |
61.6 |
65.7 |
69.9 |
74.0 |
|
B Condition (2°C) |
COPd (declared COP) |
|
3.9 |
3.9 |
3.9 |
3.5 |
3.5 |
3.7 |
3.6 |
4.0 |
3.7 |
3.8 |
3.8 |
3.9 |
3.6 |
3.7 |
3.7 |
3.9 |
4.0 |
3.7 |
3.7 |
3.6 |
3.6 |
3.7 |
3.8 |
3.9 |
|
|
Pdh (declared heating cap) |
kW |
7.4 |
8.6 |
9.9 |
11.1 |
12.5 |
15.0 |
16.7 |
18.5 |
19.9 |
21.0 |
22.4 |
24.9 |
25.0 |
27.5 |
29.2 |
32.7 |
33.5 |
33.6 |
34.9 |
36.1 |
37.5 |
40.0 |
42.5 |
45.1 |
|
C Condition (7°C) |
COPd (declared COP) |
|
6.3 |
6.4 |
6.1 |
6.1 |
6.3 |
6.7 |
6.5 |
6.3 |
6.3 |
6.1 |
6.2 |
6.5 |
6.3 |
6.5 |
6.4 |
6.5 |
6.5 |
6.3 |
6.3 |
6.2 |
6.3 |
6.5 |
6.6 |
6.8 |
|
|
Pdh (declared heating cap) |
kW |
5.0 |
5.5 |
6.4 |
7.1 |
8.0 |
9.7 |
10.7 |
11.9 |
13.0 |
13.5 |
14.4 |
16.0 |
16.1 |
17.7 |
18.8 |
21.3 |
21.6 |
21.6 |
22.4 |
23.2 |
24.1 |
25.7 |
27.4 |
29.0 |
|
D Condition (12°C) |
COPd (declared COP) |
|
7.9 |
8.2 |
7.9 |
8.5 |
8.6 |
9.0 |
9.1 |
8.2 |
8.9 |
8.8 |
9.0 |
9.0 |
9.0 |
8.8 |
8.6 |
8.7 |
8.7 |
8.6 |
8.6 |
8.7 |
8.8 |
8.9 |
9.0 |
9.0 |
|
|
Pdh (declared heating cap) |
kW |
5.9 |
5.9 |
6.3 |
4.9 |
4.9 |
7.1 |
7.1 |
6.0 |
5.7 |
6.0 |
6.4 |
7.1 |
7.1 |
7.9 |
8.3 |
13.1 |
13.1 |
9.9 |
10.0 |
10.3 |
10.7 |
12.0 |
14.2 |
14.2 |
Space heating (Average climate) recommended combination 2 |
A Condition (-7°C) |
COPd (declared COP) |
|
2.7 |
2.7 |
2.4 |
2.6 |
2.6 |
2.4 |
2.2 |
2.6 |
2.7 |
2.6 |
2.6 |
2.6 |
2.7 |
2.6 |
2.5 |
2.5 |
2.6 |
2.7 |
2.7 |
2.7 |
2.7 |
2.7 |
2.6 |
2.6 |
|
|
Pdh (declared heating cap) |
kW |
12.1 |
14.2 |
16.3 |
18.2 |
20.5 |
24.7 |
27.4 |
30.4 |
32.6 |
34.5 |
36.8 |
41.0 |
41.0 |
45.2 |
47.9 |
53.7 |
55.1 |
55.2 |
57.3 |
59.3 |
61.6 |
65.7 |
69.9 |
74.0 |
|
B Condition (2°C) |
COPd (declared COP) |
|
3.9 |
4.0 |
3.9 |
3.5 |
3.5 |
3.8 |
3.7 |
4.1 |
3.7 |
3.8 |
3.8 |
3.9 |
3.6 |
3.8 |
3.7 |
3.9 |
4.0 |
3.7 |
3.7 |
3.6 |
3.6 |
3.7 |
3.8 |
3.9 |
|
|
Pdh (declared heating cap) |
kW |
7.4 |
8.6 |
9.9 |
11.1 |
12.2 |
15.0 |
16.7 |
18.5 |
19.9 |
21.0 |
22.4 |
24.9 |
25.0 |
27.5 |
29.2 |
32.7 |
33.5 |
33.6 |
34.9 |
36.1 |
37.5 |
40.0 |
42.6 |
45.1 |
|
C Condition (7°C) |
COPd (declared COP) |
|
6.3 |
6.5 |
6.1 |
6.1 |
6.3 |
6.8 |
6.5 |
6.3 |
6.3 |
6.1 |
6.3 |
6.6 |
6.3 |
6.6 |
6.5 |
6.5 |
6.5 |
6.4 |
6.3 |
6.3 |
6.3 |
6.5 |
6.7 |
6.8 |
|
|
Pdh (declared heating cap) |
kW |
5.0 |
5.5 |
6.4 |
7.1 |
8.0 |
9.7 |
10.7 |
11.9 |
13.1 |
13.1 |
14.4 |
16.0 |
16.1 |
17.7 |
18.8 |
21.3 |
21.6 |
21.6 |
22.4 |
22.8 |
24.1 |
25.7 |
27.4 |
29.0 |
|
D Condition (12°C) |
COPd (declared COP) |
|
7.8 |
8.3 |
7.9 |
8.6 |
8.7 |
9.1 |
9.2 |
8.4 |
9.0 |
8.9 |
9.1 |
9.1 |
9.1 |
8.9 |
8.8 |
8.8 |
8.8 |
8.7 |
8.7 |
8.8 |
8.9 |
9.0 |
9.1 |
9.1 |
|
|
Pdh (declared heating cap) |
kW |
5.9 |
6.0 |
6.4 |
4.9 |
5.0 |
7.2 |
7.2 |
6.0 |
5.7 |
6.0 |
6.4 |
7.2 |
7.1 |
7.9 |
8.3 |
13.2 |
13.2 |
10.0 |
10.0 |
10.3 |
10.7 |
12.2 |
14.4 |
14.4 |
|
TBivalent |
COPd (declared COP) |
|
2.4 |
2.4 |
1.9 |
2.3 |
2.2 |
1.9 |
1.8 |
2.2 |
2.4 |
2.2 |
2.2 |
2.1 |
2.4 |
2.2 |
2.2 |
2.3 |
2.2 |
2.4 |
2.3 |
2.4 |
2.4 |
2.3 |
2.2 |
2.1 |
|
|
Pdh (declared heating cap) |
kW |
13.7 |
16.0 |
18.4 |
20.6 |
23.2 |
27.9 |
31.0 |
34.4 |
36.9 |
39.0 |
41.6 |
46.3 |
46.4 |
51.1 |
54.2 |
60.7 |
62.3 |
62.4 |
64.8 |
67.0 |
69.6 |
74.3 |
79.0 |
83.7 |
|
|
Tbiv (bivalent temperature) |
°C |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
|
TOL |
COPd (declared COP) |
|
2.4 |
2.4 |
1.9 |
2.3 |
2.2 |
1.9 |
1.8 |
2.2 |
2.4 |
2.2 |
2.2 |
2.1 |
2.4 |
2.2 |
2.2 |
2.3 |
2.2 |
2.4 |
2.3 |
2.4 |
2.4 |
2.3 |
2.2 |
2.1 |
|
|
Pdh (declared heating cap) |
kW |
13.7 |
16.0 |
18.4 |
20.6 |
23.2 |
27.9 |
31.0 |
34.4 |
36.9 |
39.0 |
41.6 |
46.3 |
46.4 |
51.1 |
54.2 |
60.7 |
62.3 |
62.4 |
64.8 |
67.0 |
69.6 |
74.3 |
79.0 |
83.7 |
|
|
Tol (temperature operating limit) |
°C |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
Space heating (Average climate) recommended combination 3 |
A Condition (-7°C) |
COPd (declared COP) |
|
2.7 |
2.6 |
2.4 |
2.6 |
2.6 |
2.4 |
2.1 |
2.6 |
2.7 |
2.6 |
2.6 |
2.5 |
2.7 |
2.6 |
2.4 |
2.5 |
2.6 |
2.7 |
2.6 |
2.7 |
2.7 |
2.6 |
2.6 |
2.5 |
|
|
Pdh (declared heating cap) |
kW |
12.1 |
14.2 |
16.3 |
18.2 |
20.5 |
24.7 |
27.4 |
30.4 |
32.6 |
34.5 |
36.8 |
41.0 |
41.0 |
45.2 |
47.9 |
53.7 |
55.1 |
55.2 |
57.3 |
59.3 |
61.6 |
65.7 |
69.9 |
74.0 |
|
B Condition (2°C) |
COPd (declared COP) |
|
3.9 |
3.7 |
3.9 |
3.5 |
3.5 |
3.7 |
3.6 |
4.0 |
3.7 |
3.8 |
3.8 |
3.9 |
3.6 |
3.7 |
3.6 |
3.8 |
3.9 |
3.7 |
3.7 |
3.6 |
3.6 |
3.6 |
3.7 |
3.8 |
|
|
Pdh (declared heating cap) |
kW |
7.4 |
8.6 |
9.9 |
11.1 |
12.5 |
15.0 |
16.7 |
18.5 |
19.9 |
21.0 |
22.4 |
24.9 |
25.0 |
27.5 |
29.2 |
32.7 |
33.5 |
33.6 |
34.9 |
36.1 |
37.5 |
40.0 |
42.5 |
45.1 |
|
C Condition (7°C) |
COPd (declared COP) |
|
6.2 |
6.4 |
6.0 |
6.1 |
6.2 |
6.5 |
6.3 |
6.2 |
6.3 |
6.1 |
6.2 |
6.3 |
6.3 |
6.4 |
6.3 |
6.3 |
6.4 |
6.3 |
6.2 |
6.2 |
6.3 |
6.4 |
6.4 |
6.5 |
|
|
Pdh (declared heating cap) |
kW |
4.9 |
5.5 |
6.4 |
7.1 |
8.0 |
9.7 |
10.7 |
11.9 |
12.9 |
13.5 |
14.4 |
16.0 |
16.1 |
17.7 |
18.8 |
21.2 |
21.6 |
21.6 |
22.4 |
23.2 |
24.1 |
25.7 |
27.3 |
29.0 |
|
D Condition (12°C) |
COPd (declared COP) |
|
7.8 |
8.1 |
7.8 |
8.5 |
8.6 |
8.7 |
8.7 |
8.2 |
8.9 |
8.8 |
9.0 |
8.6 |
9.0 |
8.9 |
8.3 |
8.5 |
8.4 |
8.6 |
8.6 |
8.7 |
8.8 |
8.7 |
8.7 |
8.7 |
|
|
Pdh (declared heating cap) |
kW |
5.8 |
5.9 |
6.2 |
4.9 |
4.9 |
6.9 |
6.9 |
6.0 |
5.7 |
6.0 |
6.4 |
7.1 |
7.1 |
7.9 |
8.3 |
12.9 |
12.8 |
9.9 |
10.0 |
10.3 |
10.7 |
11.8 |
13.7 |
13.7 |
|
TBivalent |
COPd (declared COP) |
|
2.5 |
2.4 |
2.0 |
2.3 |
2.2 |
1.9 |
1.8 |
2.3 |
2.4 |
2.2 |
2.2 |
2.1 |
2.4 |
2.2 |
2.1 |
2.2 |
2.2 |
2.4 |
2.3 |
2.4 |
2.4 |
2.2 |
2.2 |
2.1 |
|
|
Pdh (declared heating cap) |
kW |
13.7 |
16.0 |
18.4 |
20.6 |
23.2 |
27.9 |
31.0 |
34.4 |
36.9 |
39.0 |
41.6 |
46.3 |
46.4 |
51.1 |
54.2 |
60.7 |
62.3 |
62.4 |
64.8 |
67.0 |
69.6 |
74.3 |
79.0 |
83.7 |
|
|
Tbiv (bivalent temperature) |
°C |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
|
TOL |
COPd (declared COP) |
|
2.5 |
2.4 |
2.0 |
2.3 |
2.2 |
1.9 |
1.8 |
2.3 |
2.4 |
2.2 |
2.2 |
2.1 |
2.4 |
2.2 |
2.1 |
2.2 |
2.2 |
2.4 |
2.3 |
2.4 |
2.4 |
2.2 |
2.2 |
2.1 |
|
|
Pdh (declared heating cap) |
kW |
13.7 |
16.0 |
18.4 |
20.6 |
23.2 |
27.9 |
31.0 |
34.4 |
36.9 |
39.0 |
41.6 |
46.3 |
46.4 |
51.1 |
54.2 |
60.7 |
62.3 |
62.4 |
64.8 |
67.0 |
69.6 |
74.3 |
79.0 |
83.7 |
|
|
Tol (temperature operating limit) |
°C |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
Capacity range |
HP |
8 |
10 |
12 |
14 |
16 |
18 |
20 |
22 |
24 |
26 |
28 |
30 |
32 |
34 |
36 |
38 |
40 |
42 |
44 |
46 |
48 |
50 |
52 |
54 |
Maximum number of connectable indoor units |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
64 (3) |
Indoor index connection |
Min. |
|
100.0 |
125.0 |
150.0 |
175.0 |
200.0 |
225.0 |
250.0 |
275.0 |
300.0 |
325.0 |
350.0 |
375.0 |
400.0 |
425.0 |
450.0 |
475.0 |
500.0 |
525.0 |
550.0 |
575.0 |
600.0 |
625.0 |
650.0 |
675.0 |
|
Max. |
|
260.0 |
325.0 |
390.0 |
455.0 |
520.0 |
585.0 |
650.0 |
715.0 |
780.0 |
845.0 |
910.0 |
975.0 |
1,040.0 |
1,105.0 |
1,170.0 |
1,235.0 |
1,300.0 |
1,365.0 |
1,430.0 |
1,495.0 |
1,560.0 |
1,625.0 |
1,690.0 |
1,755.0 |
Dimensions |
Unit |
Height |
mm |
1,685 |
1,685 |
1,685 |
1,685 |
1,685 |
1,685 |
1,685 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Width |
mm |
930 |
930 |
930 |
1,240 |
1,240 |
1,240 |
1,240 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Depth |
mm |
765 |
765 |
765 |
765 |
765 |
765 |
765 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Weight |
Unit |
kg |
198 |
198 |
198 |
275 |
275 |
308 |
308 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fan |
External static pressure |
Max. |
Pa |
78 |
78 |
78 |
78 |
78 |
78 |
78 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Compressor |
Type |
|
Hermetically sealed scroll compressor |
Hermetically sealed scroll compressor |
Hermetically sealed scroll compressor |
Hermetically sealed scroll compressor |
Hermetically sealed scroll compressor |
Hermetically sealed scroll compressor |
Hermetically sealed scroll compressor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Operation range |
Cooling |
Min. |
°CDB |
-5.0 |
-5.0 |
-5.0 |
-5.0 |
-5.0 |
-5.0 |
-5.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Max. |
°CDB |
43.0 |
43.0 |
43.0 |
43.0 |
43.0 |
43.0 |
43.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Heating |
Min. |
°CWB |
-20.0 |
-20.0 |
-20.0 |
-20.0 |
-20.0 |
-20.0 |
-20.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Max. |
°CWB |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
15.5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Sound power level |
Cooling |
Nom. |
dBA |
78.0 (4) |
79.1 (4) |
83.4 (4) |
80.9 (4) |
85.6 (4) |
83.8 (4) |
87.9 (4) |
84.8 (4) |
86.3 (4) |
85.3 (4) |
87.6 (4) |
86.6 (4) |
88.6 (4) |
87.8 (4) |
89.9 (4) |
88.8 (4) |
87.3 (4) |
89.1 (4) |
89.8 (4) |
89.3 (4) |
90.4 (4) |
89.8 (4) |
89.3 (4) |
88.6 (4) |
Sound pressure level |
Cooling |
Nom. |
dBA |
57.0 (5) |
57.0 (5) |
61.0 (5) |
60.0 (5) |
63.0 (5) |
62.0 (5) |
65.0 (5) |
62.5 (5) |
64.0 (5) |
63.5 (5) |
65.1 (5) |
64.5 (5) |
66.0 (5) |
65.5 (5) |
67.1 (5) |
66.2 (5) |
65.2 (5) |
66.5 (5) |
67.2 (5) |
67.0 (5) |
67.8 (5) |
67.5 (5) |
67.1 (5) |
66.8 (5) |
Refrigerant |
Type |
|
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
|
GWP |
|
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
|
Charge |
kg |
5.9 |
6.0 |
6.3 |
10.3 |
11.3 |
11.7 |
11.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Charge |
TCO2Eq |
12.3 |
12.5 |
13.2 |
21.5 |
23.6 |
24.4 |
24.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Piping connections |
Liquid |
Type |
|
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
|
|
OD |
mm |
9.52 |
9.52 |
12.7 |
12.7 |
12.7 |
15.9 |
15.9 |
15.9 |
15.9 |
19.1 |
19.1 |
19.1 |
19.1 |
19.1 |
19.1 |
19.1 |
19.1 |
19.1 |
19.1 |
19.1 |
19.1 |
19.1 |
19.1 |
19.1 |
|
Gas |
Type |
|
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
|
|
OD |
mm |
19.1 |
22.2 |
28.6 |
28.6 |
28.6 |
28.6 |
28.6 |
28.6 |
34.9 |
34.9 |
34.9 |
34.9 |
34.9 |
34.9 |
41.3 |
41.3 |
41.3 |
41.3 |
41.3 |
41.3 |
41.3 |
41.3 |
41.3 |
41.3 |
|
Total piping length |
System |
Actual |
m |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
1,000 (6) |
Standard Accessories |
Installation manual |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
|
Operation manual |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
|
Connection pipes |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
Power supply |
Name |
|
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
|
Phase |
|
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
|
Frequency |
Hz |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
|
Voltage |
V |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
Notes |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
|
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
|
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
|
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
|
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
|
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
|
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
|
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
|
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
|
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
|
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
|
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
(13) - Maximum allowable voltage range variation between phases is 2%. |
|
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
|
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
(15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) |
|
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
(16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality |
|
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
(17) - Sound values are measured in a semi-anechoic room. |
|
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
|
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
|
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
|
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
(21) - For detailed contents of standard accessories, see installation/operation manual |
|
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |
(22) - Multi combination (22~54HP) data is corresponding with the standard multi combination |