Specifications Table for LRMEQ-BY1

LRMEQ3BY1 LRMEQ4BY1
Standard Accessories Installation manual Installation manual Installation manual
  General safety precautions General safety precautions General safety precautions
  Refrigerant label for F-gas regulation Refrigerant label for F-gas regulation Refrigerant label for F-gas regulation
  Auxiliary piping set Auxiliary piping set Auxiliary piping set
  Peel off F-gas label Peel off F-gas label Peel off F-gas label
  ecodesign product fiche ecodesign product fiche ecodesign product fiche
Refrigerating capacity Medium temperature Nom. kW 5.90 (1) 8.40 (1)
Annual electricity consumption Q R-410A Te -10°C kWh/a 8,698 12,651
Parameters at full load and ambient temp. 43°C R-410A Te -10°C Cooling capacity (P3) kW 5.28 7.22
      Declared COP (COP3)   1.51 1.48
      Power input (D3) kW 3.50 4.89
Weight Unit kg 126 126
Seasonal energy performance ratio SEPR R-410A Te -10°C   4.17 4.08
Refrigerant Refrigerant-=-Charge-=-TCO2Eq TCO2Eq 9.39 9.39
  GWP   2,087.5 2,087.5
  Charge kg 4.50 4.50
  Type   R-410A R-410A
Parameters at full load and ambient temp. 32°C (Point A) R-410A Te -10°C Parameters at full load and ambient temp. 32°C (Point A)-=-R-410A-=-Te -10°C-=-Rated COP (COPA)   2.33 2.30
      Rated power input (DA) kW 2.53 3.65
      Parameters at full load and ambient temp. 32°C (Point A)-=-R-410A-=-Te -10°C-=-Rated cooling capacity (PA)-=-kW kW 5.90 8.40
Fan motor Output W 70 70
  Drive   Direct drive Direct drive
Heat exchanger Type   Cross fin coil Cross fin coil
Power input Medium temperature Nom. kW 2.53 (1) 3.65 (1)
COP Medium temperature Nom.   2.33 (1) 2.30 (1)
Dimensions Unit Width mm 900 900
    Depth mm 320 320
    Height mm 1,345 1,345
Casing Colour   Daikin White Daikin White
Fan Type   Propeller Propeller
  Quantity   2 2
  Air flow rate Cooling Nom. m³/min 106 106
Power supply Phase   3N~ 3N~
  Frequency Hz 50 50
  Voltage V 380-415 380-415
Notes (1) - Cooling: evaporating temp. -10°C; outdoor temp. 32°C; suction SH10°C (1) - Cooling: evaporating temp. -10°C; outdoor temp. 32°C; suction SH10°C
  (2) - Sound pressure data: measured at 1m in front of unit, at 1.5m height (2) - Sound pressure data: measured at 1m in front of unit, at 1.5m height
  (3) - Contains fluorinated greenhouse gases (3) - Contains fluorinated greenhouse gases