| RXYSQ6T8Y1B9 | ||||
|---|---|---|---|---|
| Sound pressure level | Cooling | Nom. | dBA | 51 (4) |
| Standard Accessories | Installation manual | Installation manual | ||
| Operation manual | Operation manual | |||
| Connection pipes | Connection pipes | |||
| Capacity range | HP | 6 | ||
| Operation range | Cooling | Max. | °CDB | 46 |
| Min. | °CDB | -5 | ||
| Heating | Min. | °CWB | -20 | |
| Max. | °CWB | 15.5 | ||
| Maximum number of connectable indoor units | 64 (3) | |||
| Compressor | Type | Hermetically sealed swing compressor | ||
| Weight | Unit | kg | 104 | |
| Refrigerant | Charge | kg | 3.6 | |
| Type | R-410A | |||
| Indoor index connection | Min. | 80 | ||
| Max. | 176 | |||
| Piping connections | Liquid | OD | mm | 9.52 |
| Type | Flare connection | |||
| Gas | OD | mm | 19.1 | |
| Type | Braze connection | |||
| Heat insulation | Both liquid and gas pipes | |||
| Sound power level | Cooling | Nom. | dBA | 70 (4) |
| Dimensions | Unit | Width | mm | 900 |
| Depth | mm | 320 | ||
| Height | mm | 1,345 | ||
| Power supply | Phase | 3N~ | ||
| Name | Y1 | |||
| Frequency | Hz | 50 | ||
| Voltage | V | 380-415 | ||
| Notes | (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series. Eurovent 2015 tolerances are used. | |||
| (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series. Eurovent 2015 tolerances are used. | ||||
| (3) - Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%). | ||||
| (4) - Sound power level is an absolute value that a sound source generates. | ||||
| (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | ||||
| (6) - Sound values are measured in a semi-anechoic room. | ||||
| (7) - For detailed contents of standard accessories, see installation/operation manual | ||||
| (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | ||||
| (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | ||||
| (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | ||||
| (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | ||||
| (12) - TOCA means the total value of each OC set. | ||||
| (13) - FLA: nominal running current fan | ||||
| (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | ||||
| (15) - Maximum allowable voltage range variation between phases is 2%. | ||||