| RXYSA4A7V1B | RXYSA5A7V1B | RXYSA6A7V1B | |||||
|---|---|---|---|---|---|---|---|
| Recommended combination | 3 x FXSA25A2VEB + 1 x FXSA32A2VEB | 4 x FXSA32A2VEB | 2 x FXSA32A2VEB + 2 x FXSA40A2VEB | ||||
| Heating capacity | Nom. | 6°CWB | kW | 12.1 (2) | 14.0 (2) | 15.5 (2) | |
| COP at nom. capacity | 6°CWB | kW/kW | 4.49 | 4.20 | 4.10 | ||
| SCOP | 5.1 | 4.7 | 4.7 | ||||
| SEER | 8.2 | 7.7 | 7.6 | ||||
| Space cooling | A Condition (35°C - 27/19) | EERd | 3.4 | 3.1 | 3.0 | ||
| Pdc | kW | 12.1 | 14.0 | 15.5 | |||
| B Condition (30°C - 27/19) | EERd | 5.8 | 5.3 | 5.0 | |||
| Pdc | kW | 8.9 | 10.3 | 11.4 | |||
| C Condition (25°C - 27/19) | EERd | 10.9 | 9.8 | 9.8 | |||
| Pdc | kW | 5.7 | 6.6 | 7.3 | |||
| D Condition (20°C - 27/19) | EERd | 18.5 | 19.4 | 19.0 | |||
| Pdc | kW | 4.9 | 4.5 | 4.9 | |||
| Space heating (Average climate) | TBivalent | COPd (declared COP) | 2.8 | 2.6 | 2.5 | ||
| Pdh (declared heating cap) | kW | 8.4 | 9.7 | 10.7 | |||
| Tbiv (bivalent temperature) | °C | -10 | -10 | -10 | |||
| TOL | COPd (declared COP) | 2.8 | 2.6 | 2.5 | |||
| Pdh (declared heating cap) | kW | 8.4 | 9.7 | 10.7 | |||
| Tol (temperature operating limit) | °C | -10 | -10 | -10 | |||
| A Condition (-7°C) | COPd (declared COP) | 3.4 | 2.9 | 2.9 | |||
| Pdh (declared heating cap) | kW | 7.4 | 8.5 | 9.5 | |||
| B Condition (2°C) | COPd (declared COP) | 4.9 | 4.5 | 4.3 | |||
| Pdh (declared heating cap) | kW | 4.5 | 5.2 | 5.8 | |||
| C Condition (7°C) | COPd (declared COP) | 7.0 | 6.7 | 7.0 | |||
| Pdh (declared heating cap) | kW | 3.3 | 3.3 | 3.7 | |||
| D Condition (12°C) | COPd (declared COP) | 8.9 | 8.9 | 9.0 | |||
| Pdh (declared heating cap) | kW | 3.9 | 3.9 | 3.9 | |||
| Capacity range | HP | 4 | 5 | 6 | |||
| Maximum number of connectable indoor units | 13 (3) | 16 (3) | 18 (3) | ||||
| Indoor index connection | Min. | 50.0 | 62.5 | 70.0 | |||
| Nom. | 100 | 125 | 140 | ||||
| Max. | 130.0 | 162.5 | 182.0 | ||||
| Dimensions | Unit | Height | mm | 869 | 869 | 869 | |
| Width | mm | 1,100 | 1,100 | 1,100 | |||
| Depth | mm | 460 | 460 | 460 | |||
| Weight | Unit | kg | 102 | 102 | 102 | ||
| Fan | External static pressure | Max. | Pa | 45 | 45 | 45 | |
| Compressor | Type | Hermetically sealed swing compressor | Hermetically sealed swing compressor | Hermetically sealed swing compressor | |||
| Operation range | Cooling | Min. | °CDB | -5 | -5 | -5 | |
| Max. | °CDB | 46 | 46 | 46 | |||
| Heating | Min. | °CWB | -20 | -20 | -20 | ||
| Max. | °CWB | 16 | 16 | 16 | |||
| Sound power level | Cooling | Nom. | dBA | 67.0 (4) | 68.1 (4) | 69.0 (4) | |
| Sound pressure level | Cooling | Nom. | dBA | 49.0 (6) | 51.0 (6) | 51.0 (6) | |
| Refrigerant | Type | R-32 | R-32 | R-32 | |||
| GWP | 675.0 | 675.0 | 675.0 | ||||
| Charge | kg | 3.40 | 3.40 | 3.40 | |||
| Piping connections | Liquid | Type | Braze connection | Braze connection | Braze connection | ||
| OD | mm | 9.52 | 9.52 | 9.52 | |||
| Gas | Type | Braze connection | Braze connection | Braze connection | |||
| OD | mm | 15.9 | 15.9 | 15.9 | |||
| Total piping length | System | Actual | m | 300 (7) | 300 (7) | 300 (7) | |
| Level difference | OU - IU | Outdoor unit in highest position | m | 50 | 50 | 50 | |
| Indoor unit in highest position | m | 40 | 40 | 40 | |||
| Standard Accessories | Installation and operation manual | 1 | 1 | 1 | |||
| General safety precautions | 1 | 1 | 1 | ||||
| Peel off F-gas label | 1 | 1 | 1 | ||||
| Refrigerant label for F-gas regulation | 1 | 1 | 1 | ||||
| Tie-wraps | 2 | 2 | 2 | ||||
| Auxiliary piping set | 1 | 1 | 1 | ||||
| Caution label | 1 | 1 | 1 | ||||
| Power supply | Name | V1 | V1 | V1 | |||
| Phase | 1~ | 1~ | 1~ | ||||
| Frequency | Hz | 50 | 50 | 50 | |||
| Voltage | V | 220-240 | 220-240 | 220-240 | |||
| Notes | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | ||||
| (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | |||||
| (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. | (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. | (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. | |||||
| (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | |||||
| (5) - According to ENER Lot 21 | (5) - According to ENER Lot 21 | (5) - According to ENER Lot 21 | |||||
| (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | |||||
| (7) - Refer to refrigerant pipe selection or installation manual | (7) - Refer to refrigerant pipe selection or installation manual | (7) - Refer to refrigerant pipe selection or installation manual | |||||
| (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | |||||
| (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | |||||
| (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | |||||
| (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | |||||
| (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | |||||
| (13) - TOCA means the total value of each OC set. | (13) - TOCA means the total value of each OC set. | (13) - TOCA means the total value of each OC set. | |||||
| (14) - FLA means the nominal running current of the fan | (14) - FLA means the nominal running current of the fan | (14) - FLA means the nominal running current of the fan | |||||