|
RXYQ8T7Y1B8 |
RXYQ24T7Y1B8 |
RXYQ38T7Y1B8 |
Sound pressure level
|
Cooling
|
Nom.
|
dBA
|
58.0 (5)
|
65.0 (5)
|
67.2 (5)
|
Standard Accessories
|
Installation manual
|
1
|
1
|
1
|
|
Operation manual
|
1
|
1
|
1
|
|
Connection pipes
|
1
|
1
|
1
|
Capacity range
|
HP
|
8
|
24
|
38
|
Operation range
|
Cooling
|
Max.
|
°CDB
|
43.0
|
|
|
Min.
|
°CDB
|
-5.0
|
|
Heating
|
Min.
|
°CWB
|
-20.0
|
|
|
Max.
|
°CWB
|
15.5
|
Maximum number of connectable indoor units
|
64 (3)
|
64 (3)
|
64 (3)
|
Space cooling
|
B Condition (30°C - 27/19)
|
Pdc
|
kW
|
16.5
|
49.7
|
75.5
|
|
|
EERd
|
|
4.1
|
4.0
|
3.9
|
|
D Condition (20°C - 27/19)
|
Pdc
|
kW
|
4.8
|
14.3
|
21.6
|
|
|
EERd
|
|
8.7
|
9.5
|
10.0
|
|
A Condition (35°C - 27/19)
|
EERd
|
|
2.5
|
2.2
|
2.2
|
|
|
Pdc
|
kW
|
22.4
|
67.4
|
102.4
|
|
C Condition (25°C - 27/19)
|
EERd
|
|
6.4
|
6.7
|
6.6
|
|
|
Pdc
|
kW
|
10.6
|
31.9
|
48.5
|
SCOP
|
3.6
|
3.7
|
3.7
|
Compressor
|
Type
|
|
Hermetically sealed scroll compressor
|
Weight
|
Unit
|
kg
|
187
|
Refrigerant
|
Charge
|
TCO2Eq
|
12.3
|
|
GWP
|
|
2,087.5
|
2,087.5
|
2,087.5
|
|
Charge
|
kg
|
5.9
|
|
Type
|
|
R-410A
|
R-410A
|
R-410A
|
System
|
Outdoor unit module 2
|
|
|
RXYQ16T
|
RXYQ10T
|
|
Outdoor unit module 3
|
|
|
|
RXYQ20T
|
|
Outdoor unit module 1
|
|
|
RXYQ8T
|
RXYQ8T
|
Indoor index connection
|
Min.
|
|
100.0
|
300.0
|
475.0
|
|
Max.
|
|
260.0
|
780.0
|
1,235.0
|
Cooling capacity
|
Prated,c
|
kW
|
22.4 (1)
|
67.4 (1)
|
102.4 (1)
|
Recommended combination
|
4 x FXMQ50P7VEB
|
4 x FXMQ50P7VEB + 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB
|
6 x FXMQ50P7VEB + 10 x FXMQ63P7VEB
|
Space heating (Average climate)
|
TOL
|
COPd (declared COP)
|
|
2.0
|
1.8
|
2.1
|
|
|
Pdh (declared heating cap)
|
kW
|
13.7
|
36.9
|
58.2
|
|
|
Tol (temperature operating limit)
|
°C
|
-10
|
-10
|
-10
|
|
D Condition (12°C)
|
Pdh (declared heating cap)
|
kW
|
6.6
|
6.6
|
9.0
|
|
|
COPd (declared COP)
|
|
8.4
|
8.4
|
6.7
|
|
B Condition (2°C)
|
COPd (declared COP)
|
|
3.1
|
3.2
|
3.4
|
|
|
Pdh (declared heating cap)
|
kW
|
7.4
|
19.8
|
31.3
|
|
C Condition (7°C)
|
COPd (declared COP)
|
|
6.4
|
6.0
|
5.4
|
|
|
Pdh (declared heating cap)
|
kW
|
5.7
|
12.8
|
20.1
|
|
A Condition (-7°C)
|
COPd (declared COP)
|
|
2.3
|
2.2
|
2.4
|
|
|
Pdh (declared heating cap)
|
kW
|
12.1
|
32.6
|
51.5
|
|
TBivalent
|
Pdh (declared heating cap)
|
kW
|
13.7
|
36.9
|
58.2
|
|
|
Tbiv (bivalent temperature)
|
°C
|
-10
|
-10
|
-10
|
|
|
COPd (declared COP)
|
|
2.0
|
1.8
|
2.1
|
Piping connections
|
Liquid
|
OD
|
mm
|
9.52
|
15.9
|
19.1
|
|
|
Type
|
|
Braze connection
|
Braze connection
|
Braze connection
|
|
Total piping length
|
System
|
Actual
|
m
|
1,000 (6)
|
1,000 (6)
|
1,000 (6)
|
|
Gas
|
OD
|
mm
|
19.1
|
34.9
|
41.3
|
|
|
Type
|
|
Braze connection
|
Braze connection
|
Braze connection
|
SEER
|
5.4
|
5.5
|
5.4
|
Sound power level
|
Cooling
|
Nom.
|
dBA
|
78.0 (4)
|
86.6 (4)
|
88.9 (4)
|
Dimensions
|
Unit
|
Width
|
mm
|
930
|
|
|
Depth
|
mm
|
765
|
|
|
Height
|
mm
|
1,685
|
Fan
|
External static pressure
|
Max.
|
Pa
|
78
|
Heating capacity
|
Prated,h
|
kW
|
13.7
|
36.9
|
58.2
|
Power supply
|
Phase
|
|
3N~
|
3N~
|
3N~
|
|
Name
|
|
Y1
|
Y1
|
Y1
|
|
Frequency
|
Hz
|
50
|
50
|
50
|
|
Voltage
|
V
|
380-415
|
380-415
|
380-415
|
Notes
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
|
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
|
|
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%)
|
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%)
|
(3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%)
|
|
(4) - Sound power level is an absolute value that a sound source generates.
|
(4) - Sound power level is an absolute value that a sound source generates.
|
(4) - Sound power level is an absolute value that a sound source generates.
|
|
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
|
(6) - Refer to refrigerant pipe selection or installation manual
|
(6) - Refer to refrigerant pipe selection or installation manual
|
(6) - Refer to refrigerant pipe selection or installation manual
|
|
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
|
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
|
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
|
|
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
|
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
|
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
|
|
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
|
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
|
(9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
|
|
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
|
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
|
(10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
|
|
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
|
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
|
(11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
|
|
(12) - TOCA means the total value of each OC set.
|
(12) - TOCA means the total value of each OC set.
|
(12) - TOCA means the total value of each OC set.
|
|
(13) - FLA means the nominal running current of the fan
|
(13) - FLA means the nominal running current of the fan
|
(13) - FLA means the nominal running current of the fan
|
|
(14) - Maximum allowable voltage range variation between phases is 2%.
|
(14) - Maximum allowable voltage range variation between phases is 2%.
|
(14) - Maximum allowable voltage range variation between phases is 2%.
|
|
(15) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
(15) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
(15) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
|
(16) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature )
|
(16) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature )
|
(16) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature )
|
|
(17) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality
|
(17) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality
|
(17) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality
|
|
(18) - Sound values are measured in a semi-anechoic room.
|
(18) - Sound values are measured in a semi-anechoic room.
|
(18) - Sound values are measured in a semi-anechoic room.
|
|
(19) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
|
(19) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
|
(19) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
|
|
(20) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|
(20) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|
(20) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|
|
(21) - Ssc: Short-circuit power
|
(21) - Ssc: Short-circuit power
|
(21) - Ssc: Short-circuit power
|
|
(22) - For detailed contents of standard accessories, see installation/operation manual
|
(22) - For detailed contents of standard accessories, see installation/operation manual
|
(22) - For detailed contents of standard accessories, see installation/operation manual
|
|
(23) - Multi combination (22~54HP) data is corresponding with the standard multi combination
|
(23) - Multi combination (22~54HP) data is corresponding with the standard multi combination
|
(23) - Multi combination (22~54HP) data is corresponding with the standard multi combination
|