| RXYQ8T7Y1B8 | RXYQ24T7Y1B8 | RXYQ38T7Y1B8 | |||||
|---|---|---|---|---|---|---|---|
| Sound pressure level | Cooling | Nom. | dBA | 58.0 (5) | 65.0 (5) | 67.2 (5) | |
| Standard Accessories | Installation manual | 1 | 1 | 1 | |||
| Operation manual | 1 | 1 | 1 | ||||
| Connection pipes | 1 | 1 | 1 | ||||
| Capacity range | HP | 8 | 24 | 38 | |||
| Operation range | Cooling | Max. | °CDB | 43.0 | |||
| Min. | °CDB | -5.0 | |||||
| Heating | Min. | °CWB | -20.0 | ||||
| Max. | °CWB | 15.5 | |||||
| Maximum number of connectable indoor units | 64 (3) | 64 (3) | 64 (3) | ||||
| Space cooling | B Condition (30°C - 27/19) | Pdc | kW | 16.5 | 49.7 | 75.5 | |
| EERd | 4.1 | 4.0 | 3.9 | ||||
| D Condition (20°C - 27/19) | Pdc | kW | 4.8 | 14.3 | 21.6 | ||
| EERd | 8.7 | 9.5 | 10.0 | ||||
| A Condition (35°C - 27/19) | EERd | 2.5 | 2.2 | 2.2 | |||
| Pdc | kW | 22.4 | 67.4 | 102.4 | |||
| C Condition (25°C - 27/19) | EERd | 6.4 | 6.7 | 6.6 | |||
| Pdc | kW | 10.6 | 31.9 | 48.5 | |||
| SCOP | 3.6 | 3.7 | 3.7 | ||||
| Compressor | Type | Hermetically sealed scroll compressor | |||||
| Weight | Unit | kg | 187 | ||||
| Refrigerant | Charge | TCO2Eq | 12.3 | ||||
| GWP | 2,087.5 | 2,087.5 | 2,087.5 | ||||
| Charge | kg | 5.9 | |||||
| Type | R-410A | R-410A | R-410A | ||||
| System | Outdoor unit module 2 | RXYQ16T | RXYQ10T | ||||
| Outdoor unit module 3 | RXYQ20T | ||||||
| Outdoor unit module 1 | RXYQ8T | RXYQ8T | |||||
| Indoor index connection | Min. | 100.0 | 300.0 | 475.0 | |||
| Max. | 260.0 | 780.0 | 1,235.0 | ||||
| Cooling capacity | Prated,c | kW | 22.4 (1) | 67.4 (1) | 102.4 (1) | ||
| Recommended combination | 4 x FXMQ50P7VEB | 4 x FXMQ50P7VEB + 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB | 6 x FXMQ50P7VEB + 10 x FXMQ63P7VEB | ||||
| Space heating (Average climate) | TOL | COPd (declared COP) | 2.0 | 1.8 | 2.1 | ||
| Pdh (declared heating cap) | kW | 13.7 | 36.9 | 58.2 | |||
| Tol (temperature operating limit) | °C | -10 | -10 | -10 | |||
| D Condition (12°C) | Pdh (declared heating cap) | kW | 6.6 | 6.6 | 9.0 | ||
| COPd (declared COP) | 8.4 | 8.4 | 6.7 | ||||
| B Condition (2°C) | COPd (declared COP) | 3.1 | 3.2 | 3.4 | |||
| Pdh (declared heating cap) | kW | 7.4 | 19.8 | 31.3 | |||
| C Condition (7°C) | COPd (declared COP) | 6.4 | 6.0 | 5.4 | |||
| Pdh (declared heating cap) | kW | 5.7 | 12.8 | 20.1 | |||
| A Condition (-7°C) | COPd (declared COP) | 2.3 | 2.2 | 2.4 | |||
| Pdh (declared heating cap) | kW | 12.1 | 32.6 | 51.5 | |||
| TBivalent | Pdh (declared heating cap) | kW | 13.7 | 36.9 | 58.2 | ||
| Tbiv (bivalent temperature) | °C | -10 | -10 | -10 | |||
| COPd (declared COP) | 2.0 | 1.8 | 2.1 | ||||
| Piping connections | Liquid | OD | mm | 9.52 | 15.9 | 19.1 | |
| Type | Braze connection | Braze connection | Braze connection | ||||
| Total piping length | System | Actual | m | 1,000 (6) | 1,000 (6) | 1,000 (6) | |
| Gas | OD | mm | 19.1 | 34.9 | 41.3 | ||
| Type | Braze connection | Braze connection | Braze connection | ||||
| SEER | 5.4 | 5.5 | 5.4 | ||||
| Sound power level | Cooling | Nom. | dBA | 78.0 (4) | 86.6 (4) | 88.9 (4) | |
| Dimensions | Unit | Width | mm | 930 | |||
| Depth | mm | 765 | |||||
| Height | mm | 1,685 | |||||
| Fan | External static pressure | Max. | Pa | 78 | |||
| Heating capacity | Prated,h | kW | 13.7 | 36.9 | 58.2 | ||
| Power supply | Phase | 3N~ | 3N~ | 3N~ | |||
| Name | Y1 | Y1 | Y1 | ||||
| Frequency | Hz | 50 | 50 | 50 | |||
| Voltage | V | 380-415 | 380-415 | 380-415 | |||
| Notes | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | ||||
| (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | |||||
| (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) | (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) | (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) | |||||
| (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | |||||
| (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | |||||
| (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | |||||
| (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | |||||
| (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | |||||
| (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | |||||
| (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | |||||
| (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | |||||
| (12) - TOCA means the total value of each OC set. | (12) - TOCA means the total value of each OC set. | (12) - TOCA means the total value of each OC set. | |||||
| (13) - FLA means the nominal running current of the fan | (13) - FLA means the nominal running current of the fan | (13) - FLA means the nominal running current of the fan | |||||
| (14) - Maximum allowable voltage range variation between phases is 2%. | (14) - Maximum allowable voltage range variation between phases is 2%. | (14) - Maximum allowable voltage range variation between phases is 2%. | |||||
| (15) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (15) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (15) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | |||||
| (16) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) | (16) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) | (16) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) | |||||
| (17) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality | (17) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality | (17) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality | |||||
| (18) - Sound values are measured in a semi-anechoic room. | (18) - Sound values are measured in a semi-anechoic room. | (18) - Sound values are measured in a semi-anechoic room. | |||||
| (19) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (19) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | (19) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA | |||||
| (20) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (20) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (20) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | |||||
| (21) - Ssc: Short-circuit power | (21) - Ssc: Short-circuit power | (21) - Ssc: Short-circuit power | |||||
| (22) - For detailed contents of standard accessories, see installation/operation manual | (22) - For detailed contents of standard accessories, see installation/operation manual | (22) - For detailed contents of standard accessories, see installation/operation manual | |||||
| (23) - Multi combination (22~54HP) data is corresponding with the standard multi combination | (23) - Multi combination (22~54HP) data is corresponding with the standard multi combination | (23) - Multi combination (22~54HP) data is corresponding with the standard multi combination | |||||