Specifications Table for RXA-B9

RXA42B5V1B9
Sound pressure level Heating Nom. dBA 48.0
  Cooling Nom. dBA 48.0
Standard Accessories Drain plug 1
  Installation manual 1
  Refrigerant charge label 1
  Multilingual fluorinated greenhouse gases labels 1
  Drain cap (1) 6
  Drain cap (2) 3
Refrigerant GWP   675
  Charge kg 1.10
  Type   R-32
Operation range Cooling Ambient Max. °CDB 46
      Min. °CDB -10
  Heating Ambient Max. °CWB 18
      Min. °CWB -15
Piping connections Level difference IU - OU Max. m 20
  Additional refrigerant charge kg/m 0.02 (for piping length exceeding 10m)
Dimensions Unit Width mm 954
    Depth mm 401
    Height mm 734
Compressor Type   Hermetically sealed swing compressor
Weight Unit kg 49
Power supply Phase   1~
  Frequency Hz 50
  Voltage V 220-240
Notes (1) - See separate drawing for operation range
  (2) - See separate drawing for electrical data