Specifications Table for RQEQ-P3

RQEQ140PY13 RQEQ180PY13 RQEQ212PY13
Standard Accessories Installation manual Installation manual Installation manual Installation manual
  Operation manual Operation manual Operation manual Operation manual
  Clamps Clamps Clamps Clamps
Operation range Cooling Max. °CDB 43 43 43
    Min. °CDB -5 -5 -5
  Heating Min. °CWB -20 -20 -20
    Max. °CWB 15.5 15.5 15.5
Space cooling B Condition (30°C - 27/19) Pdc kW 10.3 13.3 14.7
    EERd   4.40 3.86 3.63
  D Condition (20°C - 27/19) Pdc kW 5.01 4.94 4.95
    EERd   9.29 9.54 9.64
  A Condition (35°C - 27/19) EERd   2.54 2.22 1.74
    Pdc kW 14.0 18.0 20.0
  C Condition (25°C - 27/19) EERd   7.31 6.89 6.57
    Pdc kW 6.63 8.53 9.47
Compressor Type   Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor
Weight Unit kg 175 175 179
Refrigerant Charge TCO2Eq 21.5 22.1 23.4
  GWP   2,087.5 2,087.5 2,087.5
  Charge kg 10.3 10.6 11.2
  Type   R-410A R-410A R-410A
Cooling capacity Prated,c kW 14.0 18.0 20.0
  Nom. kW 14.0 (1) 18.0 (1) 21.2 (1)
Space heating (Average climate) TOL COPd (declared COP)   1.92 1.84 1.64
    Pdh (declared heating cap) kW 8.5 10.6 11.9
  D Condition (12°C) Pdh (declared heating cap) kW 4.18 4.40 4.44
    COPd (declared COP)   6.43 6.82 6.88
  B Condition (2°C) COPd (declared COP)   3.42 3.56 3.92
    Pdh (declared heating cap) kW 4.58 5.72 6.41
  C Condition (7°C) COPd (declared COP)   4.84 5.26 5.40
    Pdh (declared heating cap) kW 3.29 3.68 4.12
  A Condition (-7°C) COPd (declared COP)   2.20 2.22 2.20
    Pdh (declared heating cap) kW 7.52 9.40 10.5
  TBivalent Pdh (declared heating cap) kW 8.5 10.6 11.9
    Tbiv (bivalent temperature) °C -10 -10 -10
    COPd (declared COP)   1.92 1.84 1.64
Piping connections Liquid OD mm 9.52 9.52 9.52
    Type   Braze connection Braze connection Braze connection
  Gas OD mm 15.9 19.1 19.1
    Type   Braze connection Braze connection Braze connection
  Discharge gas OD mm 12.7 15.9 15.9
    Type   Braze connection Braze connection Braze connection
Sound power level Cooling Nom. dBA 79 83 87
Dimensions Unit Width mm 635 635 635
    Depth mm 765 765 765
    Height mm 1,680 1,680 1,680
Heating capacity Prated,h kW 16.0 20.0 22.4
  Nom. kW 16.0 (2) 20.0 (2) 22.4 (2)
Power supply Phase   3~ 3~ 3~
  Name   Y1 Y1 Y1
  Frequency Hz 50 50 50
  Voltage V 380-415 380-415 380-415
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (3) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (3) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise.
  (4) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (4) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (4) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (5) - TOCA means the total value of each OC set. (5) - TOCA means the total value of each OC set. (5) - TOCA means the total value of each OC set.
  (6) - MSC means the maximum current during start up of the compressor (6) - MSC means the maximum current during start up of the compressor (6) - MSC means the maximum current during start up of the compressor
  (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (8) - Maximum allowable voltage range variation between phases is 2%. (8) - Maximum allowable voltage range variation between phases is 2%. (8) - Maximum allowable voltage range variation between phases is 2%.
  (9) - Select wire size based on the larger value of MCA or TOCA (9) - Select wire size based on the larger value of MCA or TOCA (9) - Select wire size based on the larger value of MCA or TOCA
  (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases