Specifications Table for FXFN-A2

FXFN50A2VEB FXFN71A2VEB FXFN112A2VEB
Sound pressure level Heating At high fan speed dBA 36.0 41.0 47.0
    At low fan speed dBA 31.0 33.0 39.0
    At medium fan speed dBA 34.0 37.0 44.0
  Cooling At low fan speed dBA 31.0 33.0 38.0
    At high fan speed dBA 35.0 40.0 46.0
    At medium fan speed dBA 33.0 36.0 43.0
Standard Accessories Installation and operation manual 1 1 1
  Drain hose 1 1 1
  Clamp for drain hose 1 1 1
  Washer for hanger bracket 8 8 8
  Screws 4 4 4
  Installation guide 1 1 1
  Insulation for fitting 2 2 2
  Sealing pads 1 1 1
  Wire clamp material 7 7 7
  Clamps 1 1 1
Refrigerant GWP   1 1 1
  Type   R744 (CO2) R744 (CO2) R744 (CO2)
Power input - 50Hz Cooling At high fan speed kW 0.019 0.046 0.096
  Heating At high fan speed kW 0.019 0.046 0.096
Cooling capacity Total capacity At high fan speed kW 5.60 8.00 12.50
Piping connections Liquid OD mm 9.52 9.52 9.52
    Type   Braze connection Braze connection Braze connection
  Gas OD mm 12.70 12.70 12.70
    Type   Braze connection Braze connection Braze connection
  Drain   VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25)
Sound power level Cooling At high fan speed dBA 53.0 58.0 63.0
Air filter Type   Resin net Resin net Resin net
Dimensions Unit Width mm 840 840 840
    Depth mm 840 840 840
    Height mm 246 246 288
Casing Material   Galvanised steel plate Galvanised steel plate Galvanised steel plate
Weight Unit kg 26 26 29
Decoration panel 2 Weight kg 10.3 10.3 10.3
  Model   BYCQ140E2GFW1, BYCQ140E2GFW1B BYCQ140E2GFW1, BYCQ140E2GFW1B BYCQ140E2GFW1, BYCQ140E2GFW1B
  Dimensions Depth mm 950 950 950
    Width mm 950 950 950
    Height mm 148 148 148
Decoration panel 3 Dimensions Depth mm 950 950 950
    Height mm 106 106 106
    Width mm 950 950 950
  Model   BYCQ140E2P, BYCQ140E2PB BYCQ140E2P, BYCQ140E2PB BYCQ140E2P, BYCQ140E2PB
  Weight kg 6.5 6.5 6.5
Fan Air flow rate - 50Hz Cooling At high fan speed m³/min 15.5 23.2 32.7
      At low fan speed m³/min 10.7 13.8 20.6
Decoration panel Weight kg 5.5 5.5 5.5
  Model   BYCQ140E2W1, BYCQ140E2W1W, BYCQ140E2W1B BYCQ140E2W1, BYCQ140E2W1W, BYCQ140E2W1B BYCQ140E2W1, BYCQ140E2W1W, BYCQ140E2W1B
  Dimensions Height mm 65 65 65
    Depth mm 950 950 950
    Width mm 950 950 950
Heating capacity Total capacity At high fan speed kW 6.30 9.00 14.00
Current - 50Hz Maximum fuse amps (MFA) A 6 6 6
Power supply Phase   1~ 1~ 1~
  Frequency Hz 50/60 50/60 50/60
  Voltage V 220-240/220 220-240/220 220-240/220
Notes (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB
  (3) - The sound power level is an absolute value indicating the power which a sound source generates. (3) - The sound power level is an absolute value indicating the power which a sound source generates. (3) - The sound power level is an absolute value indicating the power which a sound source generates.
  (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%.
  (6) - MCA/MFA: MCA = 1.1 x FLA (6) - MCA/MFA: MCA = 1.1 x FLA (6) - MCA/MFA: MCA = 1.1 x FLA
  (7) - Instead of a fuse, use a circuit breaker (7) - Instead of a fuse, use a circuit breaker (7) - Instead of a fuse, use a circuit breaker
  (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA (8) - Select wire size based on the value of MCA
  (9) - BYCQ140E2W1: pure white standard panel with grey louvers; BYCQ140E2W1W: pure white standard panel with white louvers; BYCQ140E2W1B: black standard panel with black louvers. (9) - BYCQ140E2W1: pure white standard panel with grey louvers; BYCQ140E2W1W: pure white standard panel with white louvers; BYCQ140E2W1B: black standard panel with black louvers. (9) - BYCQ140E2W1: pure white standard panel with grey louvers; BYCQ140E2W1W: pure white standard panel with white louvers; BYCQ140E2W1B: black standard panel with black louvers.
  (10) - The BYCQ140E2W1W has white insulations. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the BYCQ140E2W1W decoration panel in enviroments exposed to concentrations of dirt. (10) - The BYCQ140E2W1W has white insulations. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the BYCQ140E2W1W decoration panel in enviroments exposed to concentrations of dirt. (10) - The BYCQ140E2W1W has white insulations. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the BYCQ140E2W1W decoration panel in enviroments exposed to concentrations of dirt.
  (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases