FVA71AMVEB / RZAG71M7Y1B |
FVA100AMVEB / RZAG71M7Y1B |
FVA100AMVEB / RZAG100M7Y1B |
FVA140AMVEB / RZAG100M7Y1B |
FVA125AMVEB / RZAG125M7Y1B |
FVA140AMVEB / RZAG140M7Y1B |
Cooling capacity
|
Nom.
|
kW
|
6.80 (1)
|
6.80 (1)
|
9.50 (1)
|
9.50 (1)
|
12.1 (1)
|
13.4 (1)
|
Space cooling
|
Annual energy consumption
|
kWh/a
|
374
|
371
|
554
|
517
|
1,133
|
1,314
|
|
Capacity
|
Pdesign
|
kW
|
6.80
|
6.80
|
9.50
|
9.50
|
12.1
|
13.4
|
Space heating (Average climate)
|
Capacity
|
Pdesign
|
kW
|
4.70
|
4.70
|
7.80
|
7.80
|
9.52
|
9.52
|
|
Annual energy consumption
|
kWh/a
|
1,625
|
1,625
|
2,600
|
2,697
|
3,209
|
3,383
|
Heating capacity
|
Nom.
|
kW
|
7.50 (2)
|
7.50 (2)
|
10.8 (2)
|
10.8 (2)
|
13.5 (2)
|
15.5 (2)
|
Space cooling
|
SEER
|
|
6.37
|
6.41
|
6.00
|
6.43
|
6.41
|
6.12
|
|
Energy efficiency class
|
|
A++
|
A++
|
A+
|
A++
|
Space heating (Average climate)
|
SCOP/A
|
|
4.05
|
4.05
|
4.20
|
4.05
|
4.15
|
3.94
|
|
Energy efficiency class
|
|
A+
|
A+
|
A+
|
A+
|
Notes
|
(1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
|
(1) - Cooling: T2: indoor temp. 26,6°CDB, 19,4°CWB, outdoor temp. 48°CDB [Btu/hr/W]
|
(1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
|
(1) - Cooling: T2: indoor temp. 26,6°CDB, 19,4°CWB, outdoor temp. 48°CDB [Btu/hr/W]
|
(1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
|
(1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
|
|
(2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
|
(2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
|
(2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
|
(2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
|
(2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
|
(2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
|
|
(3) - See separate drawing for operation range
|
|
(3) - See separate drawing for operation range
|
|
(3) - See separate drawing for operation range
|
(3) - See separate drawing for operation range
|
|
(4) - See separate drawing for electrical data
|
|
(4) - See separate drawing for electrical data
|
|
(4) - See separate drawing for electrical data
|
(4) - See separate drawing for electrical data
|