Specifications Table for FFQ-B9V

FFQ25B9V1B (Archived) FFQ35B9V1B (Archived) FFQ50B9V1B (Archived) FFQ60B9V1B (Archived)
Sound pressure level Cooling Low dBA 24.5 25 27 32
    High dBA 29.5 32 36 41
Standard Accessories Operation manual Operation manual Operation manual Operation manual Operation manual
  Installation manual Installation manual Installation manual Installation manual Installation manual
  Paper pattern for installation Paper pattern for installation Paper pattern for installation Paper pattern for installation Paper pattern for installation
  Drain hose Drain hose Drain hose Drain hose Drain hose
  Clamp metal Clamp metal Clamp metal Clamp metal Clamp metal
  Washer fixing plate Washer fixing plate Washer fixing plate Washer fixing plate Washer fixing plate
  Sealing pads Sealing pads Sealing pads Sealing pads Sealing pads
  Clamps Clamps Clamps Clamps Clamps
  Screws Screws Screws Screws Screws
  Washer for hanger bracket Washer for hanger bracket Washer for hanger bracket Washer for hanger bracket Washer for hanger bracket
  Insulation for fitting Insulation for fitting Insulation for fitting Insulation for fitting Insulation for fitting
Cooling capacity Total capacity Nom. kW 2.5 (1) 3.4 (1) 4.7 (1) 5.8 (1)
Piping connections Liquid OD mm 6.35 6.35 6.35 6.35
  Gas OD mm 9.52 9.52 12.7 12.7
  Drain   VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26)
Sound power level Cooling dBA 46.5 49 53 58
Dimensions Unit Width mm 575 575 575 575
    Depth mm 575 575 575 575
    Height mm 286 286 286 286
Casing Material   Galvanised steel Galvanised steel Galvanised steel Galvanised steel
  Colour   Unpainted Unpainted Unpainted Unpainted
Weight Unit kg 17.5 17.5 17.5 17.5
Decoration panel Weight kg 2.7 2.7 2.7 2.7
  Model   BYFQ60BW1 BYFQ60BW1 BYFQ60BW1 BYFQ60BW1
  Dimensions Height mm 55 55 55 55
    Depth mm 700 700 700 700
    Width mm 700 700 700 700
  Colour   Pure White (RAL 9010) Pure White (RAL 9010) Pure White (RAL 9010) Pure White (RAL 9010)
Heating capacity Total capacity Nom. kW 3.2 (2) 4.5 (2) 5.5 (2) 7.0 (2)
Power supply Phase   1~ 1~ 1~ 1~
  Name   V1 V1 V1 V1
  Frequency Hz 50 50 50 50
  Voltage V 220-240 220-240 220-240 220-240
Notes (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m
  (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
  (4) - Nominal cooling and heating capactity is depending on the outdoor unit type (4) - Nominal cooling and heating capactity is depending on the outdoor unit type (4) - Nominal cooling and heating capactity is depending on the outdoor unit type (4) - Nominal cooling and heating capactity is depending on the outdoor unit type
  (5) - PED unit category: Art3§3: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC (5) - PED unit category: Art3§3: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC (5) - PED unit category: Art3§3: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC (5) - PED unit category: Art3§3: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC