Specifications Table for FBA-A(9) / RXM-R9

FBA35A2VEB9 / RXM35R5V1B9
Cooling capacity Nom. kW 3.40
Heating capacity Nom. kW 4.00
Nominal efficiency EER   4.02
  COP   4.02
  Annual energy consumption kWh 423
  Energy labeling Directive Cooling   A
    Heating   A
Space cooling Energy efficiency class   A++
  Capacity Pdesign kW 3.40
  SEER   6.23
  Annual energy consumption kWh/a 191
Space heating (Average climate) Energy efficiency class   A+
  Capacity Pdesign kW 2.90
  SCOP/A   4.07
  Annual energy consumption kWh/a 996
Notes (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
  (3) - See separate drawing for operation range
  (4) - See separate drawing for electrical data