Specifications Table for FBA-A(9) / RXM-R

FBA35A2VEB9 / RXM35R5V1B FBA50A2VEB9 / RXM50R2V1B FBA50A2VEB9 / RXM50R5V1B FBA60A2VEB9 / RXM60R2V1B FBA60A2VEB9 / RXM60R5V1B
Cooling capacity Nom. kW 3.40 5.00 5.00 5.70 5.70
Space cooling SEER   6.23 6.27 6.27 5.91 5.91
  Annual energy consumption kWh/a 191 279 279 336 336
  Capacity Pdesign kW 3.40 5.00 5.00 5.70 5.70
  Energy efficiency class   A++ A++ A++ A+ A+
Space heating (Average climate) Capacity Pdesign kW 2.90 4.40 4.40 4.60 4.60
  SCOP/A   4.07 4.06 4.06 4.01 4.01
  Energy efficiency class   A+ A+ A+ A+ A+
  Pdh Heating capacity at -10° kW     3.73   3.99
  Annual energy consumption kWh/a 996 1,517 1,517 1,607 1,607
Nominal efficiency EER   4.02 3.55 3.55 3.48 3.48
  Annual energy consumption kWh 423 704 704 819 819
  COP   4.02 3.83 3.83 3.71 3.71
  Energy labeling Directive Cooling   A A A A A
    Heating   A A A A A
Heating capacity Nom. kW 4.00 5.50 5.50 7.00 7.00
Notes (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
  (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range
  (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data