Specifications Table for EWYA-DV3P-H-

EWYA004D2V3P-H EWYA006D2V3P-H EWYA008D2V3P-H EWYA009DAV3P-H- EWYA011DAV3P-H- EWYA014DAV3P-H- EWYA016DAV3P-H-
Cooling capacity Nom. kW 4.86 (1), 4.52 (2) 5.83 (1), 5.09 (2) 6.18 (1), 5.44 (2) 9.35 (1), 9.10 (2) 11.6 (1), 11.5 (2) 12.8 (1), 12.7 (2) 14.0 (1), 15.3 (2)
Capacity control Method   Variable (inverter) Variable (inverter) Variable (inverter) Variable (inverter) Variable (inverter) Variable (inverter) Variable (inverter)
Power input Cooling Nom. kW 0.820 (1), 1.36 (2) 1.08 (1), 1.55 (2) 1.19 (1), 1.73 (2) 2.79 (1), 1.71 (2) 3.56 (1), 2.17 (2) 4.06 (1), 2.51 (2) 4.58 (1), 3.24 (2)
EER 5.91 (1), 3.32 (2) 5.40 (1), 3.28 (2) 5.19 (1), 3.14 (2) 3.35 (1), 5.34 (2) 3.26 (1), 5.31 (2) 3.16 (1), 5.04 (2) 3.06 (1), 4.74 (2)
SEER       5.62 (5) 5.79 (5) 5.71 (5) 5.59 (5)
Dimensions Unit Depth mm 362 362 362 460 460 460 460
    Height mm 770 770 770 870 870 870 870
    Width mm 1,250 1,250 1,250 1,380 1,380 1,380 1,380
Weight Unit kg 88.0 88.0 88.0 147 147 147 147
Casing Colour   Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white
  Material   Zinc coated low carbon steel Zinc coated low carbon steel Zinc coated low carbon steel Polyester painted galvanised steel plate Polyester painted galvanised steel plate Polyester painted galvanised steel plate Polyester painted galvanised steel plate
Air heat exchanger Type         High efficiency fin and tube type with integral subcooler High efficiency fin and tube type with integral subcooler High efficiency fin and tube type with integral subcooler High efficiency fin and tube type with integral subcooler
Fan Quantity   1 1 1 1 1 1 1
  Type   Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan motor Drive         Direct drive Direct drive Direct drive Direct drive
Compressor Quantity   1 1 1 1 1 1 1
  Type   Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing inverter compressor Hermetically sealed swing inverter compressor Hermetically sealed swing inverter compressor Hermetically sealed swing inverter compressor
  Starting method         Inverter driven Inverter driven Inverter driven Inverter driven
Operation range Air side Cooling Min. °CDB 10 (3) 10 (3) 10 (3) 10 10 10 10
      Max. °CDB 43 43 43 43 43 43 43
  Water side Evaporator Min. °CDB 5 (3) 5 (3) 5 (3) 5 5 5 5
      Max. °CDB 22 22 22 22 22 22 22
Sound power level Cooling Nom. dBA 61.0 (1) 62.0 (1) 62.0 (1) 65.5 67.0 69.0 69.0
Sound pressure level Cooling Nom. dBA 48.0 (1) 49.0 (1) 50.0 (1) 44.0 47.7 50.8 51.0
Refrigerant Type   R-32 R-32 R-32 R-32 R-32 R-32 R-32
  GWP   675.0 675.0 675.0 675.0 675.0 675.0 675.0
  Charge kg 1.35 1.35 1.35
  Circuits Quantity         1 1 1 1
Power supply Phase   1~ 1~ 1~ 1~ 1~ 1~ 1~
  Frequency Hz 50 50 50 50 50 50 50
  Voltage V 230 +/-10% 230 +/-10% 230 +/-10% 230 230 230 230
  Voltage range Min. %       -10 -10 -10 -10
    Max. %       10 10 10 10
Unit Running current Max A       30.8 30.8 30.8 30.8
Notes (1) - Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (1) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (1) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (1) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB
  (2) - Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) (2) - Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) (2) - Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) (2) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (2) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (2) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (2) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB
  (3) - For more details, see operation range drawing (3) - For more details, see operation range drawing (3) - For more details, see operation range drawing (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
        (4) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (4) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (4) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (4) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
        (5) - According to EN14825 (5) - According to EN14825 (5) - According to EN14825 (5) - According to EN14825
        (6) - Depends on operation mode, refer to installation manual. (6) - Depends on operation mode, refer to installation manual. (6) - Depends on operation mode, refer to installation manual. (6) - Depends on operation mode, refer to installation manual.
        (7) - For more details, see operation range drawing (7) - For more details, see operation range drawing (7) - For more details, see operation range drawing (7) - For more details, see operation range drawing