Specifications Table for EWWQ-KBW1N

EWWQ014KBW1N EWWQ025KBW1N EWWQ033KBW1N EWWQ049KBW1N EWWQ064KBW1N EWWQ098KBW1N EWWQ113KBW1N EWWQ128KBW1N EWWQ147KBW1N EWWQ162KBW1N EWWQ177KBW1N EWWQ192KBW1N
Sound pressure level Cooling Nom. dBA           55.71 59.71 61.71 56.9 60.9 61.9 62.9
Refrigerant Circuits Quantity             4 4 4 6 6 6 6
  Charge kg           9.4 10.2 11.2 13.8 14.8 15.8 16.8
  Type             R-410A R-410A R-410A R-410A R-410A R-410A R-410A
Cooling capacity Nom. kW           94 108 122 142 155 169 183
Power input Cooling Nom. kW           22.7 25.8 28.9 33.9 37 40.1 43.2
Sound power level Cooling Nom. dBA           71 75 77 73 77 78 79
Dimensions Unit Width mm           600 600 600 600 600 600 600
    Depth mm           1,200 1,200 1,200 1,200 1,200 1,200 1,200
    Height mm           1,200 1,200 1,200 1,800 1,800 1,800 1,800
Compressor Type             Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor
  Quantity             4 4 4 6 6 6 6
Water heat exchanger - condenser Type             Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate
  Water flow rate Nom. l/s           5.57 6.39 7.21 8.35 9.17 10 10.8
Capacity control Minimum capacity %           25 25 25 16 16 16 16
Weight Operation weight kg           640 673 707 960 993 1,026 1,060
  Unit kg           620 650 680 930 960 990 1,020
Water heat exchanger - evaporator Water flow rate Nom. l/s           4.5 5.2 5.8 6.8 7.4 8.1 8.8
  Type             Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate
  Water volume l           9 10 12 14 15 16 18
EER 4.209 4.177 4.164 4.127 4.182 4.17 4.19 4.22 4.18 4.2 4.22 4.24
ESEER 4.52 4.58 4.72 4.56 4.71 4.65 4.64 4.66 4.7 4.69 4.70 4.71
Power supply Phase             3~ 3~ 3~ 3~ 3~ 3~ 3~
  Frequency Hz           50 50 50 50 50 50 50
  Voltage V           400 400 400 400 400 400 400
Notes (1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C (1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C (1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C (1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C (1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C (1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C (1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C (1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C (1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C (1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C (1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C (1) - Nominal cooling capacities are based on the following conditions. Evaporator: 12°C/7°C; condenser: 30°C/35°C
  (2) - The nominal sound power level is measured according to ISO9614 (2) - The nominal sound power level is measured according to ISO9614 (2) - The nominal sound power level is measured according to ISO9614 (2) - The nominal sound power level is measured according to ISO9614 (2) - The nominal sound power level is measured according to ISO9614 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
  (3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (3) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
  (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
  (5) - Electrical data referred to standard unit without options, refer to name plate data. (5) - Electrical data referred to standard unit without options, refer to name plate data. (5) - Electrical data referred to standard unit without options, refer to name plate data. (5) - Electrical data referred to standard unit without options, refer to name plate data. (5) - Electrical data referred to standard unit without options, refer to name plate data. (5) - Electrical data referred to standard unit without options, refer to name plate data. (5) - Electrical data referred to standard unit without options, refer to name plate data. (5) - Electrical data referred to standard unit without options, refer to name plate data. (5) - Electrical data referred to standard unit without options, refer to name plate data. (5) - Electrical data referred to standard unit without options, refer to name plate data. (5) - Electrical data referred to standard unit without options, refer to name plate data. (5) - Electrical data referred to standard unit without options, refer to name plate data.
Cooling capacity Nom. kW 13.25 23.9 30.4 47.15 60.98
Capacity control Method   Fixed Fixed Fixed Fixed Fixed
  Minimum capacity % 100 100 100 50 50
Power input Cooling Nom. kW 3.15 5.72 7.3 11.42 14.58
Dimensions Unit Depth mm 600 600 600 1200 1200
    Height mm 600 600 600 600 600
    Width mm 600 600 600 600 600
Weight Unit kg 120 170 175 310 340
  Operation weight kg 123 175 182 320 353
Water heat exchanger - evaporator Type   Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate
  Water volume l 1.23 1.93 2.68 4.5 5.93
  Water flow rate Nom. l/s 0.64 1.15 1.46 2.26 2.92
Water heat exchanger - condenser Type   Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate
  Water flow rate Nom. l/s 0.78 1.41 1.83 2.78 3.61
Compressor Type   Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor
  Quantity   1 1 1 2 2
Sound power level Cooling Nom. dBA 64 64 71 67 74
Sound pressure level Cooling Nom. dBA 50 50 57 53 60
Refrigerant Type   R-410A R-410A R-410A R-410A R-410A
  Charge kg 1.2 2 3.1 4.6 5.6
  Circuits Quantity   1 1 1 2 2
Space heating Average climate water outlet 35°C General Seasonal space heating eff. class   A+++ A+++ A+++ A+++ A+++
Energy Efficiency Range Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F
Power supply Name   W1 W1 W1 W1 W1
  Phase   3~ 3~ 3~ 3~ 3~
  Frequency Hz 50 50 50 50 50
  Voltage V 400 400 400 400 400