Specifications Table for EWWQ-G-SS

EWWQ090G-SS EWWQ100G-SS EWWQ120G-SS EWWQ130G-SS EWWQ150G-SS EWWQ170G-SS EWWQ190G-SS EWWQ210G-SS EWWQ240G-SS EWWQ300G-SS EWWQ360G-SS
Sound pressure level Cooling Nom. dBA 64 67 69 70 72 72 72 74 76 76 77
Refrigerant Circuits Quantity   1 1 1 1 1 1 1 1 1 1 1
  GWP   2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5
  Charge kg 10 10 11 11 12 12 15 16 17 19 20
  Type   R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
Operation range Condenser Cooling Min. °CDB 25
      Max. °CDB 55
  Evaporator Cooling Min. °CDB -10
      Max. °CDB 15
Cooling capacity Nom. kW 93.7 105.6 119 135.9 150 172.1 193.8 220.7 246.1 314.3 370.4
Power input Cooling Nom. kW 21.3 24 26.9 30.5 33.9 38.9 43.8 50.74 56.1 70.2 84
Sound power level Cooling Nom. dBA 80 83 85 87 88 88 88 90 92 93 93
Refrigerant charge Refrigerant charge-=-Per circuit-=-TCO2Eq TCO2Eq 20.88 20.88 22.96 22.96 25.05 25.05 31.31 33.40 35.49 39.66 41.75
Dimensions Unit Width mm 928 928 928 928 928 928 928 928 928 928 928
    Depth mm 2,432 2,432 2,264 2,264 2,264 2,432 2,432 2,432 2,432 2,432 2,432
    Height mm 1,066 1,066 1,066 1,066 1,066 1,066 1,066 1,066 1,066 1,186 1,186
Compressor Type   Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor
  Quantity   2 2 2 2 2 2 2 2 2 2 2
Water heat exchanger - condenser Type   Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger
  Water flow rate Nom. l/s 5.52 6.23 7.05 8.04 8.87 10.17 11.43 13.02 14.53 18.46 21.81
Capacity control Minimum capacity % 50 43 50 44 50 45 50 43 50 40 50
  Method   Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed
Weight Operation weight kg 554.9 652.4 781.6 821.4 859 901.4 945.9 1,009.6 1,023.2 1,194.7 1,311.1
  Unit kg 516 606 728 762 795 832 871 921 934 1,083 1,181
Water heat exchanger - evaporator Water flow rate Nom. l/s 4.5 5.07 5.7 6.51 7.18 8.24 9.28 10.57 11.79 15.06 17.74
  Type   Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger
  Water volume l 6 8 8 10 12 13 15 17 17 27 34
EER 4.399 4.4 4.424 4.456 4.425 4.424 4.425 4.349 4.387 4.477 4.41
ESEER 5.51 5.52 5.51 5.53 5.51 5.53 5.52 5.52 5.52 5.52 5.52
Power supply Phase   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Frequency Hz 50 50 50 50 50 50 50 50 50 50 50
  Voltage V 400 400 400 400 400 400 400 400 400 400 400
Notes (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation.
  (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 5/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 5/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 5/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 5/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 5/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 5/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 5/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 5/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 5/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 5/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 5/10°C; condensor 40/45°C, unit at full load operation
  (3) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (3) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (3) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (3) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (3) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (3) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (3) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (3) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (3) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (3) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (3) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units
  (4) - Fluid: Water (4) - Fluid: Water (4) - Fluid: Water (4) - Fluid: Water (4) - Fluid: Water (4) - Fluid: Water (4) - Fluid: Water (4) - Fluid: Water (4) - Fluid: Water (4) - Fluid: Water (4) - Fluid: Water
  (5) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (5) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (5) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (5) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (5) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (5) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (5) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (5) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (5) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (5) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (5) - For more details on the operating limits please refer to the Chiller Selection Software (CSS).
  (6) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (6) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (6) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (6) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (6) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (6) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (6) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (6) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (6) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (6) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (6) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
  (7) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (7) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (7) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (7) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (7) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (7) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (7) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (7) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (7) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (7) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (7) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
  (8) - Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load (8) - Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load (8) - Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load (8) - Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load (8) - Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load (8) - Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load (8) - Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load (8) - Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load (8) - Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load (8) - Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load (8) - Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load
  (9) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (9) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (9) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (9) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (9) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (9) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (9) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (9) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (9) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (9) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (9) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current
  (10) - Maximum running current is based on max compressor absorbed current in its envelope (10) - Maximum running current is based on max compressor absorbed current in its envelope (10) - Maximum running current is based on max compressor absorbed current in its envelope (10) - Maximum running current is based on max compressor absorbed current in its envelope (10) - Maximum running current is based on max compressor absorbed current in its envelope (10) - Maximum running current is based on max compressor absorbed current in its envelope (10) - Maximum running current is based on max compressor absorbed current in its envelope (10) - Maximum running current is based on max compressor absorbed current in its envelope (10) - Maximum running current is based on max compressor absorbed current in its envelope (10) - Maximum running current is based on max compressor absorbed current in its envelope (10) - Maximum running current is based on max compressor absorbed current in its envelope
  (11) - Maximum unit current for wires sizing is based on minimum allowed voltage. (11) - Maximum unit current for wires sizing is based on minimum allowed voltage. (11) - Maximum unit current for wires sizing is based on minimum allowed voltage. (11) - Maximum unit current for wires sizing is based on minimum allowed voltage. (11) - Maximum unit current for wires sizing is based on minimum allowed voltage. (11) - Maximum unit current for wires sizing is based on minimum allowed voltage. (11) - Maximum unit current for wires sizing is based on minimum allowed voltage. (11) - Maximum unit current for wires sizing is based on minimum allowed voltage. (11) - Maximum unit current for wires sizing is based on minimum allowed voltage. (11) - Maximum unit current for wires sizing is based on minimum allowed voltage. (11) - Maximum unit current for wires sizing is based on minimum allowed voltage.
  (12) - Maximum current for wires sizing: compressor full load ampere x 1.1 (12) - Maximum current for wires sizing: compressor full load ampere x 1.1 (12) - Maximum current for wires sizing: compressor full load ampere x 1.1 (12) - Maximum current for wires sizing: compressor full load ampere x 1.1 (12) - Maximum current for wires sizing: compressor full load ampere x 1.1 (12) - Maximum current for wires sizing: compressor full load ampere x 1.1 (12) - Maximum current for wires sizing: compressor full load ampere x 1.1 (12) - Maximum current for wires sizing: compressor full load ampere x 1.1 (12) - Maximum current for wires sizing: compressor full load ampere x 1.1 (12) - Maximum current for wires sizing: compressor full load ampere x 1.1 (12) - Maximum current for wires sizing: compressor full load ampere x 1.1