EWWD600VZSSA1 |
EWWD700VZSSA1 |
EWWD760VZSSA1 |
EWWD890VZSSA1 |
EWWDC10VZSSA1 |
EWWDC12VZSSA2 |
EWWDC13VZSSA2 |
EWWDC14VZSSA2 |
EWWDC16VZSSA2 |
EWWDC17VZSSA2 |
EWWDC19VZSSA2 |
EWWDC21VZSSA2 |
Cooling capacity
|
Nom.
|
kW
|
610
|
704
|
757
|
894
|
1,039
|
1,173
|
1,288
|
1,381
|
1,552
|
1,722
|
1,876
|
2,051
|
Capacity control
|
Method
|
|
Variable
|
Variable
|
Variable
|
Variable
|
Variable
|
Variable
|
Variable
|
Variable
|
Variable
|
Variable
|
Variable
|
Variable
|
|
Minimum capacity
|
%
|
20
|
20
|
20
|
20
|
20
|
10
|
10
|
10
|
10
|
10
|
10
|
10
|
Power input
|
Cooling
|
Nom.
|
kW
|
110
|
132
|
142
|
162
|
196
|
231
|
252
|
276
|
315
|
339
|
380
|
404
|
EER
|
5.5
|
5.31
|
5.3
|
5.52
|
5.29
|
5.07
|
5.11
|
5
|
4.93
|
5.08
|
4.93
|
5.08
|
ESEER
|
7.62
|
7.5
|
7.63
|
7.54
|
7.52
|
7.86
|
7.81
|
7.9
|
7.46
|
7.99
|
7.49
|
7.95
|
Dimensions
|
Unit
|
Depth
|
mm
|
3,722
|
3,750
|
3,750
|
3,690
|
3,822
|
4,792
|
4,792
|
4,792
|
4,792
|
4,508
|
4,508
|
4,750
|
|
|
Height
|
mm
|
2,123
|
2,123
|
2,123
|
2,292
|
2,487
|
2,296
|
2,296
|
2,296
|
2,296
|
2,350
|
2,338
|
2,498
|
|
|
Width
|
mm
|
1,178
|
1,179
|
1,179
|
1,233
|
1,303
|
1,484
|
1,487
|
1,487
|
1,484
|
1,580
|
1,627
|
1,753
|
Weight
|
Unit
|
kg
|
2,892
|
2,928
|
2,941
|
3,451
|
4,237
|
5,570
|
5,790
|
5,820
|
6,220
|
6,890
|
7,260
|
8,260
|
|
Operation weight
|
kg
|
2,977
|
3,033
|
3,053
|
3,611
|
4,488
|
5,980
|
6,220
|
6,290
|
6,690
|
7,480
|
7,830
|
9,070
|
Water heat exchanger - evaporator
|
Type
|
|
Flooded shell and tube
|
Flooded shell and tube
|
Flooded shell and tube
|
Flooded shell and tube
|
Flooded shell and tube
|
Flooded shell and tube
|
Flooded shell and tube
|
Flooded shell and tube
|
Flooded shell and tube
|
Flooded shell and tube
|
Flooded shell and tube
|
Flooded shell and tube
|
|
Water volume
|
l
|
88
|
88
|
96
|
134
|
156
|
230
|
230
|
270
|
270
|
320
|
320
|
380
|
Water heat exchanger - condenser
|
Type
|
|
Shell and tube
|
Shell and tube
|
Shell and tube
|
Shell and tube
|
Shell and tube
|
Shell and tube
|
Shell and tube
|
Shell and tube
|
Shell and tube
|
Shell and tube
|
Shell and tube
|
Shell and tube
|
Compressor
|
Type
|
|
Inverter driven single screw compressor
|
Inverter driven single screw compressor
|
Inverter driven single screw compressor
|
Inverter driven single screw compressor
|
Inverter driven single screw compressor
|
Inverter driven single screw compressor
|
Inverter driven single screw compressor
|
Inverter driven single screw compressor
|
Inverter driven single screw compressor
|
Inverter driven single screw compressor
|
Inverter driven single screw compressor
|
Inverter driven single screw compressor
|
|
Quantity
|
|
1
|
1
|
1
|
1
|
1
|
2
|
2
|
2
|
2
|
2
|
2
|
2
|
Sound power level
|
Cooling
|
Nom.
|
dBA
|
101
|
105
|
105
|
105
|
107
|
106
|
106
|
107
|
107
|
108
|
108
|
110
|
Sound pressure level
|
Cooling
|
Nom.
|
dBA
|
82
|
86
|
86
|
86
|
88
|
87
|
87
|
88
|
88
|
89
|
89
|
90
|
Operation range
|
Evaporator
|
Cooling
|
Min.
|
°CDB
|
-3
|
-3
|
-3
|
-3
|
-3
|
-3
|
-3
|
-3
|
-3
|
-3
|
-3
|
-3
|
|
|
|
Max.
|
°CDB
|
20
|
20
|
20
|
20
|
20
|
20
|
20
|
20
|
20
|
20
|
20
|
20
|
|
Condenser
|
Cooling
|
Min.
|
°CDB
|
16
|
16
|
16
|
16
|
16
|
16
|
16
|
16
|
16
|
16
|
16
|
16
|
|
|
|
Max.
|
°CDB
|
63
|
63
|
63
|
63
|
63
|
63
|
63
|
63
|
63
|
63
|
63
|
63
|
Refrigerant
|
Type
|
|
R-134a
|
R-134a
|
R-134a
|
R-134a
|
R-134a
|
R-134a
|
R-134a
|
R-134a
|
R-134a
|
R-134a
|
R-134a
|
R-134a
|
|
Charge
|
kg
|
100
|
110
|
110
|
170
|
180
|
250
|
260
|
290
|
290
|
320
|
320
|
350
|
|
Circuits
|
Quantity
|
|
1
|
1
|
1
|
1
|
1
|
2
|
2
|
2
|
2
|
2
|
2
|
2
|
|
GWP
|
|
1,430
|
1,430
|
1,430
|
1,430
|
1,430
|
1,430
|
1,430
|
1,430
|
1,430
|
1,430
|
1,430
|
1,430
|
Power supply
|
Phase
|
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
|
Frequency
|
Hz
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
|
Voltage
|
V
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
Notes
|
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
|
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
|
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
|
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
|
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
|
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
|
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
|
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
|
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
|
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
|
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
|
(1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
|
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
(2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
|
|
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
(3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
|
|
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C
|
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C
|
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C
|
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C
|
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C
|
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C
|
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C
|
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C
|
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C
|
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C
|
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C
|
(4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C
|
|
(5) - Maximum running current is based on max compressor absorbed current in its envelope
|
(5) - Maximum running current is based on max compressor absorbed current in its envelope
|
(5) - Maximum running current is based on max compressor absorbed current in its envelope
|
(5) - Maximum running current is based on max compressor absorbed current in its envelope
|
(5) - Maximum running current is based on max compressor absorbed current in its envelope
|
(5) - Maximum running current is based on max compressor absorbed current in its envelope
|
(5) - Maximum running current is based on max compressor absorbed current in its envelope
|
(5) - Maximum running current is based on max compressor absorbed current in its envelope
|
(5) - Maximum running current is based on max compressor absorbed current in its envelope
|
(5) - Maximum running current is based on max compressor absorbed current in its envelope
|
(5) - Maximum running current is based on max compressor absorbed current in its envelope
|
(5) - Maximum running current is based on max compressor absorbed current in its envelope
|
|
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage.
|
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage.
|
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage.
|
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage.
|
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage.
|
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage.
|
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage.
|
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage.
|
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage.
|
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage.
|
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage.
|
(6) - Maximum unit current for wires sizing is based on minimum allowed voltage.
|
|
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1
|
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1
|
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1
|
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1
|
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1
|
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1
|
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1
|
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1
|
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1
|
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1
|
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1
|
(7) - Maximum current for wires sizing: compressor full load ampere x 1.1
|
|
(8) - All data refers to the standard unit without options.
|
(8) - All data refers to the standard unit without options.
|
(8) - All data refers to the standard unit without options.
|
(8) - All data refers to the standard unit without options.
|
(8) - All data refers to the standard unit without options.
|
(8) - All data refers to the standard unit without options.
|
(8) - All data refers to the standard unit without options.
|
(8) - All data refers to the standard unit without options.
|
(8) - All data refers to the standard unit without options.
|
(8) - All data refers to the standard unit without options.
|
(8) - All data refers to the standard unit without options.
|
(8) - All data refers to the standard unit without options.
|
|
(9) - All data are subject to change without notice. Please refer to the unit nameplate data.
|
(9) - All data are subject to change without notice. Please refer to the unit nameplate data.
|
(9) - All data are subject to change without notice. Please refer to the unit nameplate data.
|
(9) - All data are subject to change without notice. Please refer to the unit nameplate data.
|
(9) - All data are subject to change without notice. Please refer to the unit nameplate data.
|
(9) - All data are subject to change without notice. Please refer to the unit nameplate data.
|
(9) - All data are subject to change without notice. Please refer to the unit nameplate data.
|
(9) - All data are subject to change without notice. Please refer to the unit nameplate data.
|
(9) - All data are subject to change without notice. Please refer to the unit nameplate data.
|
(9) - All data are subject to change without notice. Please refer to the unit nameplate data.
|
(9) - All data are subject to change without notice. Please refer to the unit nameplate data.
|
(9) - All data are subject to change without notice. Please refer to the unit nameplate data.
|
|
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS).
|
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS).
|
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS).
|
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS).
|
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS).
|
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS).
|
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS).
|
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS).
|
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS).
|
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS).
|
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS).
|
(10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS).
|
|
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
(11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
|
|
(12) - In case of inverter driven units, no inrush current at start up is experienced.
|
(12) - In case of inverter driven units, no inrush current at start up is experienced.
|
(12) - In case of inverter driven units, no inrush current at start up is experienced.
|
(12) - In case of inverter driven units, no inrush current at start up is experienced.
|
(12) - In case of inverter driven units, no inrush current at start up is experienced.
|
(12) - In case of inverter driven units, no inrush current at start up is experienced.
|
(12) - In case of inverter driven units, no inrush current at start up is experienced.
|
(12) - In case of inverter driven units, no inrush current at start up is experienced.
|
(12) - In case of inverter driven units, no inrush current at start up is experienced.
|
(12) - In case of inverter driven units, no inrush current at start up is experienced.
|
(12) - In case of inverter driven units, no inrush current at start up is experienced.
|
(12) - In case of inverter driven units, no inrush current at start up is experienced.
|