Specifications Table for EWWD-VZSS

EWWD600VZSSA1 EWWD700VZSSA1 EWWD760VZSSA1 EWWD890VZSSA1 EWWDC10VZSSA1 EWWDC12VZSSA2 EWWDC13VZSSA2 EWWDC14VZSSA2 EWWDC16VZSSA2 EWWDC17VZSSA2 EWWDC19VZSSA2 EWWDC21VZSSA2
Cooling capacity Nom. kW 610 704 757 894 1,039 1,173 1,288 1,381 1,552 1,722 1,876 2,051
Capacity control Method   Variable Variable Variable Variable Variable Variable Variable Variable Variable Variable Variable Variable
  Minimum capacity % 20 20 20 20 20 10 10 10 10 10 10 10
Power input Cooling Nom. kW 110 132 142 162 196 231 252 276 315 339 380 404
EER 5.5 5.31 5.3 5.52 5.29 5.07 5.11 5 4.93 5.08 4.93 5.08
ESEER 7.62 7.5 7.63 7.54 7.52 7.86 7.81 7.9 7.46 7.99 7.49 7.95
Dimensions Unit Depth mm 3,722 3,750 3,750 3,690 3,822 4,792 4,792 4,792 4,792 4,508 4,508 4,750
    Height mm 2,123 2,123 2,123 2,292 2,487 2,296 2,296 2,296 2,296 2,350 2,338 2,498
    Width mm 1,178 1,179 1,179 1,233 1,303 1,484 1,487 1,487 1,484 1,580 1,627 1,753
Weight Unit kg 2,892 2,928 2,941 3,451 4,237 5,570 5,790 5,820 6,220 6,890 7,260 8,260
  Operation weight kg 2,977 3,033 3,053 3,611 4,488 5,980 6,220 6,290 6,690 7,480 7,830 9,070
Water heat exchanger - evaporator Type   Flooded shell and tube Flooded shell and tube Flooded shell and tube Flooded shell and tube Flooded shell and tube Flooded shell and tube Flooded shell and tube Flooded shell and tube Flooded shell and tube Flooded shell and tube Flooded shell and tube Flooded shell and tube
  Water volume l 88 88 96 134 156 230 230 270 270 320 320 380
Water heat exchanger - condenser Type   Shell and tube Shell and tube Shell and tube Shell and tube Shell and tube Shell and tube Shell and tube Shell and tube Shell and tube Shell and tube Shell and tube Shell and tube
Compressor Type   Inverter driven single screw compressor Inverter driven single screw compressor Inverter driven single screw compressor Inverter driven single screw compressor Inverter driven single screw compressor Inverter driven single screw compressor Inverter driven single screw compressor Inverter driven single screw compressor Inverter driven single screw compressor Inverter driven single screw compressor Inverter driven single screw compressor Inverter driven single screw compressor
  Quantity   1 1 1 1 1 2 2 2 2 2 2 2
Sound power level Cooling Nom. dBA 101 105 105 105 107 106 106 107 107 108 108 110
Sound pressure level Cooling Nom. dBA 82 86 86 86 88 87 87 88 88 89 89 90
Operation range Evaporator Cooling Min. °CDB -3 -3 -3 -3 -3 -3 -3 -3 -3 -3 -3 -3
      Max. °CDB 20 20 20 20 20 20 20 20 20 20 20 20
  Condenser Cooling Min. °CDB 16 16 16 16 16 16 16 16 16 16 16 16
      Max. °CDB 63 63 63 63 63 63 63 63 63 63 63 63
Refrigerant Type   R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a
  Charge kg 100 110 110 170 180 250 260 290 290 320 320 350
  Circuits Quantity   1 1 1 1 1 2 2 2 2 2 2 2
  GWP   1,430 1,430 1,430 1,430 1,430 1,430 1,430 1,430 1,430 1,430 1,430 1,430
Power supply Phase   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
  Voltage V 400 400 400 400 400 400 400 400 400 400 400 400
Notes (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; condenser 30/35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
  (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (2) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
  (3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (3) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
  (4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C (4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C (4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C (4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C (4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C (4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C (4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C (4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C (4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C (4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C (4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C (4) - Nominal running current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; condenser 30°C/35°C
  (5) - Maximum running current is based on max compressor absorbed current in its envelope (5) - Maximum running current is based on max compressor absorbed current in its envelope (5) - Maximum running current is based on max compressor absorbed current in its envelope (5) - Maximum running current is based on max compressor absorbed current in its envelope (5) - Maximum running current is based on max compressor absorbed current in its envelope (5) - Maximum running current is based on max compressor absorbed current in its envelope (5) - Maximum running current is based on max compressor absorbed current in its envelope (5) - Maximum running current is based on max compressor absorbed current in its envelope (5) - Maximum running current is based on max compressor absorbed current in its envelope (5) - Maximum running current is based on max compressor absorbed current in its envelope (5) - Maximum running current is based on max compressor absorbed current in its envelope (5) - Maximum running current is based on max compressor absorbed current in its envelope
  (6) - Maximum unit current for wires sizing is based on minimum allowed voltage. (6) - Maximum unit current for wires sizing is based on minimum allowed voltage. (6) - Maximum unit current for wires sizing is based on minimum allowed voltage. (6) - Maximum unit current for wires sizing is based on minimum allowed voltage. (6) - Maximum unit current for wires sizing is based on minimum allowed voltage. (6) - Maximum unit current for wires sizing is based on minimum allowed voltage. (6) - Maximum unit current for wires sizing is based on minimum allowed voltage. (6) - Maximum unit current for wires sizing is based on minimum allowed voltage. (6) - Maximum unit current for wires sizing is based on minimum allowed voltage. (6) - Maximum unit current for wires sizing is based on minimum allowed voltage. (6) - Maximum unit current for wires sizing is based on minimum allowed voltage. (6) - Maximum unit current for wires sizing is based on minimum allowed voltage.
  (7) - Maximum current for wires sizing: compressor full load ampere x 1.1 (7) - Maximum current for wires sizing: compressor full load ampere x 1.1 (7) - Maximum current for wires sizing: compressor full load ampere x 1.1 (7) - Maximum current for wires sizing: compressor full load ampere x 1.1 (7) - Maximum current for wires sizing: compressor full load ampere x 1.1 (7) - Maximum current for wires sizing: compressor full load ampere x 1.1 (7) - Maximum current for wires sizing: compressor full load ampere x 1.1 (7) - Maximum current for wires sizing: compressor full load ampere x 1.1 (7) - Maximum current for wires sizing: compressor full load ampere x 1.1 (7) - Maximum current for wires sizing: compressor full load ampere x 1.1 (7) - Maximum current for wires sizing: compressor full load ampere x 1.1 (7) - Maximum current for wires sizing: compressor full load ampere x 1.1
  (8) - All data refers to the standard unit without options. (8) - All data refers to the standard unit without options. (8) - All data refers to the standard unit without options. (8) - All data refers to the standard unit without options. (8) - All data refers to the standard unit without options. (8) - All data refers to the standard unit without options. (8) - All data refers to the standard unit without options. (8) - All data refers to the standard unit without options. (8) - All data refers to the standard unit without options. (8) - All data refers to the standard unit without options. (8) - All data refers to the standard unit without options. (8) - All data refers to the standard unit without options.
  (9) - All data are subject to change without notice. Please refer to the unit nameplate data. (9) - All data are subject to change without notice. Please refer to the unit nameplate data. (9) - All data are subject to change without notice. Please refer to the unit nameplate data. (9) - All data are subject to change without notice. Please refer to the unit nameplate data. (9) - All data are subject to change without notice. Please refer to the unit nameplate data. (9) - All data are subject to change without notice. Please refer to the unit nameplate data. (9) - All data are subject to change without notice. Please refer to the unit nameplate data. (9) - All data are subject to change without notice. Please refer to the unit nameplate data. (9) - All data are subject to change without notice. Please refer to the unit nameplate data. (9) - All data are subject to change without notice. Please refer to the unit nameplate data. (9) - All data are subject to change without notice. Please refer to the unit nameplate data. (9) - All data are subject to change without notice. Please refer to the unit nameplate data.
  (10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (10) - For more details on the operating limits please refer to the Chiller Selection Software (CSS).
  (11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (11) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.
  (12) - In case of inverter driven units, no inrush current at start up is experienced. (12) - In case of inverter driven units, no inrush current at start up is experienced. (12) - In case of inverter driven units, no inrush current at start up is experienced. (12) - In case of inverter driven units, no inrush current at start up is experienced. (12) - In case of inverter driven units, no inrush current at start up is experienced. (12) - In case of inverter driven units, no inrush current at start up is experienced. (12) - In case of inverter driven units, no inrush current at start up is experienced. (12) - In case of inverter driven units, no inrush current at start up is experienced. (12) - In case of inverter driven units, no inrush current at start up is experienced. (12) - In case of inverter driven units, no inrush current at start up is experienced. (12) - In case of inverter driven units, no inrush current at start up is experienced. (12) - In case of inverter driven units, no inrush current at start up is experienced.