Specifications Table for EWAT-B-SR

EWAT085B-SRB1 EWAT115B-SRB1 EWAT135B-SRB1 EWAT155B-SRB2 EWAT175B-SRB1 EWAT195B-SRB2 EWAT205B-SRB2 EWAT215B-SRB1 EWAT240B-SRB2 EWAT260B-SRB2 EWAT290B-SRB1 EWAT310B-SRB2 EWAT310B-SRC1 EWAT320B-SRC2 EWAT330B-SRB2 EWAT340B-SRB1 EWAT350B-SRB2 EWAT350B-SRC1 EWAT380B-SRC2 EWAT420B-SRB2 EWAT430B-SRC2 EWAT460B-SRB2 EWAT480B-SRC2 EWAT510B-SRB2 EWAT570B-SRB2 EWAT570B-SRC2 EWAT610B-SRB2 EWAT620B-SRC2 EWAT670B-SRB2 EWAT670B-SRC2 EWAT730B-SRC2 EWAT790B-SRC2 EWAT860B-SRC2 EWAT960B-SRC2 EWAT085B-SRA1 (Archived) EWAT115B-SRA1 (Archived) EWAT135B-SRA1 (Archived) EWAT155B-SRA2 (Archived) EWAT175B-SRA1 (Archived) EWAT195B-SRA2 (Archived) EWAT205B-SRA2 (Archived) EWAT215B-SRA1 (Archived) EWAT240B-SRA2 (Archived) EWAT260B-SRA2 (Archived) EWAT290B-SRA1 (Archived) EWAT310B-SRA2 (Archived) EWAT330B-SRA2 (Archived) EWAT340B-SRA1 (Archived) EWAT350B-SRA2 (Archived) EWAT420B-SRA2 (Archived) EWAT460B-SRA2 (Archived) EWAT510B-SRA2 (Archived) EWAT570B-SRA2 (Archived) EWAT610B-SRA2 (Archived) EWAT670B-SRA2 (Archived)
Sound pressure level Cooling Nom. dBA 61.2 (1) 64.7 (1) 66.4 (1) 63.3 (1) 68.3 (1) 65.3 (1) 66.6 (1) 69.4 (1) 68.1 (1) 68.2 (1) 68.5 (1) 68.7 (1) 68.8 68.8 68.8 (1) 69.6 (1) 68.9 (1) 69.0 69.8 69.8 (1) 69.9 69.9 (1) 70.0 70.5 (1) 70.5 (1) 70.6 70.6 (1) 70.7 71.1 (1) 70.8 71.2 71.2 71.5 71.6 61.2 64.7 66.4 63.3 68.3 65.3 66.6 69.4 68.1 68.2 68.5 68.7 68.8 69.6 68.9 69.8 69.9 70.5 70.5 70.6 71.1
Operation range Air side Cooling Min. °CDB                                                                     -10 -10 -10 -10 -10 -10 -10 -10 -18 -18 -18 -18 -18 -18 -18 -18 -18 -18 -18 -18 -18
      Max. °CDB                                                                     43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43
  Water side Cooling Max. °CDB                                                                     20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
      Min. °CDB                                                                     -13 -13 -13 -13 -13 -13 -13 -13 -13 -13 -13 -13 -13 -13 -13 -13 -13 -13 -13 -13 -13
Compressor Type   Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression Driven vapour compression
  Starting method   Direct on line Direct on line Direct on line   Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line   Direct on line       Direct on line       Direct on line   Direct on line   Direct on line Direct on line   Direct on line   Direct on line
  Quantity   2 2 2 4 2 4 4 2 4 4 3 4 3 3 4 3 4 4 4 4 4 5 5 5 6 5 6 6 6 6 6 7 7 8 2 2 2 4 2 4 4 2 4 4 3 4 4 3 4 4 5 5 6 6 6
Weight Operation weight kg 696 783 830 1,035 1,006 1,198 1,190 1,210 1,826 1,853 2,020 2,308 2,187 2,234 2,336 2,454 2,364 2,316 2,733 2,852 2,959 3,094 3,099 3,251 3,526 3,694 3,960 3,905 4,321 4,014 4,544 4,922 5,375 5,611 696 783 830 1,035 1,006 1,198 1,190 1,210 1,822 1,849 1,951 2,268 2,296 2,350 2,324 2,784 2,954 3,111 3,360 3,762 4,089
  Unit kg 691 777 821 1,028 994 1,187 1,179 1,194 1,815 1,842 2,004 2,289 2,164 2,206 2,317 2,434 2,345 2,288 2,705 2,824 2,920 3,066 3,063 3,223 3,484 3,634 3,918 3,828 4,279 3,937 4,467 4,845 5,298 5,512 689 773 820 1,026 993 1,185 1,177 1,191 1,815 1,843 1,935 2,251 2,277 2,330 2,304 2,754 2,921 3,078 3,312 3,718 4,053
Air heat exchanger Type   Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel
EER 2.27 2.61 2.34 2.28 2.26 2.48 2.37 2.21 2.6 2.49 2.31 2.44 2.757 2.634 2.41 2.7 2.35 2.502 3.003 2.71 2.771 2.45 2.586 2.48 2.32 2.969 2.37 2.801 2.55 2.674 2.844 2.762 2.907 2.738 2.26 2.6 2.33 2.27 2.26 2.47 2.36 2.21 2.59 2.48 2.3 2.44 2.41 2.69 2.35 2.7 2.43 2.46 2.31 2.35 2.53
ESEER                                                                     3.95 4.07 3.9 3.81 4.1 3.88 3.97 3.73 4.09 3.89 4.12 4.05 3.96 4.2 3.97 4.09 4.13 4.02 4.13 4.01 4.1
Refrigerant GWP         675             675       675   675                                   675 675 675 675 675 675 675 675 675 675 675 675 675 675 675 675 675 675 675 675 675
  Type   R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32
  Circuits Quantity         2             1       2   2                                   1 1 1 2 1 2 2 1 2 2 1 2 2 1 2 2 2 2 2 2 2
  Charge kg 7.1 8.4 8.4 13 10.7 13.9 14.4 12.3 18.2 18.8 19 25.7 22 25 25 25.5 24 30 31 34.3 35 35.5 39 40.6 41.5 45 44.4 50 44.7 53 59 63 68 77 10 11 12.5 15 14 18 18 17 36 38 36 42 43 50 44 57 58 60 62 80 90
Cooling capacity Nom. kW 76 105 124 150 165 181 201 204 231 249 266 290 297.62 308.38 312 330 331 334.14 373.60 398 415.25 444 463.29 488 534 553.35 579 605.02 638 647.77 714.95 768.57 835.75 933.57 76.32 104.78 123.67 149.61 164.58 180.89 199.92 203.05 230.33 247.63 265.52 289.52 310.75 328.17 329.79 397.33 441.96 486.05 532.44 576.51 634.99
Water heat exchanger Water volume l       7             16       19   19                                   5 6 9 7 12 11 11 16 11 11 16 19 19 20 19 28 28 28 42 42 42
  Type         Brazed plate             Brazed plate       Brazed plate   Brazed plate                                   Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate
Power input Cooling Nom. kW       65.9             115       129   140                                   33.8 40.3 53.1 65.9 72.8 73.2 84.7 91.9 89.1 100 115 118 129 122 140 147 181 197 230 244 251
Sound power level Cooling Nom. dBA 78.6 (1) 82.5 (1) 84.1 (1) 81.6 (1) 86.3 (1) 83.9 (1) 85.2 (1) 87.8 (1) 87 (1) 87.2 (1) 87.5 (1) 88.2 (1) 87.9 87.8 88.3 (1) 89.1 (1) 88.4 (1) 88.1 89.5 89.8 (1) 89.6 89.8 (1) 89.7 90.4 (1) 90.5 (1) 90.8 91 (1) 90.9 91.8 (1) 91.0 91.9 91.9 92.6 92.7 78.6 82.5 84.1 81.6 86.3 83.9 85.2 87.8 87 87.2 87.5 88.2 88.3 89.1 88.4 89.8 89.8 90.4 90.5 91 91.8
Dimensions Unit Width mm 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 2,236 2,236 2,236 2,236 2,238 2,238 2,236 2,236 2,236 2,238 2,238 2,236 2,238 2,236 2,238 2,236 2,236 2,238 2,236 2,238 2,236 2,238 2,238 2,238 2,238 2,238 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236
    Depth mm 2,120 2,660 2,660 3,570 3,180 4,170 4,170 3,780 2,326 2,326 2,326 3,226 2,514 2,514 3,226 3,226 3,226 2,514 3,594 4,126 3,594 4,126 3,594 4,126 4,126 4,674 5,025 4,674 5,874 4,674 5,754 5,848 6,928 6,928 2,120 2,660 2,660 3,570 3,180 4,170 4,170 3,780 2,326 2,326 2,326 3,226 3,226 3,226 3,226 4,126 4,126 4,126 4,126 5,025 5,874
    Height mm 1,801 1,801 1,801 1,822 1,801 1,822 1,822 1,822 2,540 2,540 2,540 2,540 2,535 2,535 2,540 2,540 2,540 2,535 2,535 2,540 2,535 2,540 2,535 2,540 2,540 2,535 2,540 2,535 2,540 2,535 2,535 2,535 2,535 2,535 1,801 1,801 1,801 1,822 1,801 1,822 1,822 1,822 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540
Capacity control Minimum capacity % 50 38 50 25 38 21 19 50 17 25 24 14 22 21 13 33 19 19 18 17 16 15 14 14 12 22 11 20 17 18 17 15 14 25 50 38 50 25 38 21 19 50 17 25 24 14 13 33 19 17 15 14 12 11 17
  Method   Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Step Staged Staged Staged Variable Staged Variable Variable Staged Variable Variable Variable Variable Variable Variable Variable Variable Variable Variable Variable Variable Variable
Water heat exchanger - evaporator Water pressure drop Cooling Nom. kPa                         46.76 44.30       51.80 64.25   69.54   86.14     20.47   24.22   18.52 22.34 25.63 30.07 29.62
  Water volume l                         22.95 27.27       27.27 27.27   35.37   35.37     58.80   58.80   75.60 75.60 75.60 75.60 92.40
Fan Air flow rate Nom. l/s       11,352             17,064       21,330   21,330                                   4,929 7,396 7,396 11,352 9,838 14,202 14,202 12,325 17,064 17,064 17,064 21,330 21,330 25,596 21,330 29,862 29,862 34,128 34,128 38,394 46,926
    Cooling Nom. l/s                         21,470 21,460       21,470 32,200   32,200   32,200     42,940   42,940   42,940 53,670 53,670 64,400 64,400
  Speed rpm       1,200             780       780   780                                   1,200 1,200 1,200 1,200 1,200 1,200 1,200 1,200 780 780 780 780 780 780 780 780 780 780 780 780 780
Compressor Starting method         Direct on line             Direct on line       Direct on line   Direct on line                                   Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line
Power supply Phase   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Voltage range Max. % 10 10 10   10 10 10 10 10 10   10 10 10   10   10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
    Min. % -10 -10 -10   -10 -10 -10 -10 -10 -10   -10 0 0   -10   0 0 -10 0 -10 0 -10 -10 0 -10 0 -10 0 0 0 0 0
  Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Voltage V                         400 400       400 400   400   400     400   400   400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
Unit Max unit current for wires sizing A 76 106 102   174 204 200 181 207 204   257 269 273   273   316 332 356 379 437 428 445 526 487 534 537 544 584 642 693 752 849
  Starting current Max A 213 313 324   462 384 395 498 410 420   573 693 697   588   735 750 636 792 681 838 719 763 891 801 936 843 979 1,032 1,078 1,131 1,219
  Running current Cooling Nom. A 62 71 87   119 123 139 151 151 165   202 195 210   202   236 232 245 272 298 319 324 378 344 402 392 414 434 459 503 529 615
    Max A 73 86 96   132 156 167 168 182 193   243 245 249   258   287 302 307 344 351 390 389 433 443 471 488 513 531 584 630 683 771
Notes (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0     (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0     (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0   (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0   (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0   (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0   (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0           (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
  (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only     (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only     (2) - The value refers to the pressure drop in the evaporator only   (2) - The value refers to the pressure drop in the evaporator only   (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only   (2) - The value refers to the pressure drop in the evaporator only   (2) - The value refers to the pressure drop in the evaporator only           (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281
  (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1     (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1     (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1   (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1   (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1   (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1   (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1           (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i
  (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level.     (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level.     (4) - The certification refers only to the overall sound power level.   (4) - The certification refers only to the overall sound power level.   (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level.   (4) - The certification refers only to the overall sound power level.   (4) - The certification refers only to the overall sound power level.           (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition
  (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding     (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding     (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding   (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding   (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding   (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding   (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding           (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.
  (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition     (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition     (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition   (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition   (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition   (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition   (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition           (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options.
  (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.     (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.     (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.   (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.   (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.   (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.   (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.           (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data.
  (8) - Fluid: Water (8) - Fluid: Water (8) - Fluid: Water (8) - Fluid: Water (8) - Fluid: Water (8) - Fluid: Water (8) - Fluid: Water (8) - Fluid: Water (8) - Fluid: Water (8) - Fluid: Water (8) - Fluid: Water (8) - Fluid: Water     (8) - Fluid: Water (8) - Fluid: Water (8) - Fluid: Water     (8) - Fluid: Water   (8) - Fluid: Water   (8) - Fluid: Water (8) - Fluid: Water   (8) - Fluid: Water   (8) - Fluid: Water           (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only
  (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.     (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.     (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.   (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.   (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.   (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.   (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.           (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans
  (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.     (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.     (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.   (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.   (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.   (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.   (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.           (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
  (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current     (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current     (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current   (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current   (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current   (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current   (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current           (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced.
  (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.     (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.     (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.   (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.   (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.   (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.   (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.           (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current.
  (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.     (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.     (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.   (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.   (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.   (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.   (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.           (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
  (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1     (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1     (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1   (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1   (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1   (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1   (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1           (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage.
  (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options.     (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options.     (15) - The data are referred to the unit without additional options.   (15) - The data are referred to the unit without additional options.   (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options.   (15) - The data are referred to the unit without additional options.   (15) - The data are referred to the unit without additional options.           (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1
  (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book     (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book     (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book   (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book   (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book   (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book   (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book           (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book
Space cooling ηs,c % 161 173 161   166.2 162.2 167.8 161 179.8 164.2   172.2       179       179   179.8   179.4 179   179   179
Refrigerant GWP   675 675 675   675 675 675 675 675 675   675 675 675   675   675 675 675 675 675 675 675 675 675 675 675 675 675 675 675 675 675
  Circuits Quantity   1 1 1   1 2 2 1 2 2   2 1 2   1   1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Fan motor Drive   Phase cut Phase cut Phase cut   Phase cut Phase cut Phase cut Phase cut VFD driven VFD driven   VFD driven Brushless Brushless   VFD driven   Brushless Brushless VFD driven Brushless VFD driven Brushless VFD driven VFD driven Brushless VFD driven Brushless VFD driven Brushless Brushless Brushless Brushless Brushless
IPLV 4.67 4.97 4.5   4.74 4.64 4.91 4.66 4.93 4.27   4.82 5.485 4.999   5   5.319 5.324 4.81 5.339 4.92 5.382 4.93 5.04 5.557 5.03 5.557 5.01 5.525 5.650 5.484 5.630 5.550
Piping connections Evaporator water inlet/outlet (OD)   76.1 76.1 76.1   76.1 88.9 88.9 76.1 88.9 88.9   88.9 88.9mm 88.9mm   76.1   88.9mm 88.9mm 88.9 88.9mm 88.9 88.9mm 88.9 114.3 139.7mm 114.3 139.7mm 114.3 139.7mm 139.7mm 139.7mm 139.7mm 139.7mm
SEER 4.1 4.4 4.1   4.23 4.13 4.27 4.1 4.57 4.18   4.38 5.013 4.700   4.55   4.806 4.895 4.55 4.913 5.57 4.902 4.56 4.55 5.124 4.55 5.083 4.55 5.022 5.206 5.232 5.284 5.121
Power input Cooling Nom. kW 33.7 40.3 53   73 73.2 84.6 91.9 89 99.9   119 108.0 117.1   122   133.5 124.4 147 149.9 181 179.2 197 230 186.4 244 216.0 251 242.2 251.4 278.3 287.5 341.0
Casing Material   Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet   Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet   Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet   Galvanized and painted steel sheet   Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet
  Colour   Ivory white Ivory white Ivory white   Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white   Ivory white Ivory white Ivory white   Ivory white   Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white
Fan Type   Direct propeller Direct propeller Direct propeller   Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller   Direct propeller Direct propeller Direct propeller   Direct propeller   Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller
  Quantity   4 6 6   8 10 10 10 4 4   5 4 4   6   4 6 7 6 7 6 8 8 8 9 8 11 8 10 10 12 12
Notes (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.
Water heat exchanger - evaporator Type                           Brazed plate Brazed plate       Brazed plate Brazed plate   Brazed plate   Brazed plate     Brazed plate   Brazed plate   Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate
Operation range Air side Cooling Min. °CDB                         -20 -20       -20 -20   -20   -20     -20   -20   -20 -20 -20 -20 -20
      Max. °CDB                         52 52       52 52