Specifications Table for EWAA-DW1P

EWAA011DAW1P EWAA014DAW1P EWAA016DAW1P
Sound pressure level Cooling Nom. dBA 47.7 50.8 51.0
Hydraulic components Expansion vessel Volume l 8 8 8
Operation range Air side Cooling Min. °CDB 10 10 10
      Max. °CDB 43 43 43
  Water side Cooling Max. °CDB 22 22 22
      Min. °CDB 5 5 5
Refrigerant charge Per circuit kg 3.80 3.80 3.80
  Refrigerant charge-=-Per circuit-=-TCO2Eq TCO2Eq 2.6 2.6 2.6
Compressor Type   Hermetically sealed swing inverter compressor Hermetically sealed swing inverter compressor Hermetically sealed swing inverter compressor
  Starting method   Inverter driven Inverter driven Inverter driven
  Quantity   1 1 1
Weight Unit kg 147 147 147
Air heat exchanger Type   High efficiency fin and tube type with integral subcooler High efficiency fin and tube type with integral subcooler High efficiency fin and tube type with integral subcooler
EER 3.26 (1), 5.31 (2) 3.16 (1), 5.04 (2) 3.06 (1), 4.74 (2)
Refrigerant GWP   675.0 675.0 675.0
  Type   R-32 R-32 R-32
  Circuits Quantity   1 1 1
  Control   Electronic expansion valve Electronic expansion valve Electronic expansion valve
Fan motor Speed Cooling Nom. rpm 550 650 650
Cooling capacity Nom. kW 11.6 (1), 11.5 (2) 12.8 (1), 12.7 (2) 14.0 (1), 15.3 (2)
Water heat exchanger Water volume l 2 2 2
  Minimum water volume in the system l 20 (6) 20 (6) 20 (6)
  Type   Plate heat exchanger Plate heat exchanger Plate heat exchanger
Power input Cooling Nom. kW 3.56 (1), 2.17 (2) 4.06 (1), 2.51 (2) 4.58 (1), 3.24 (2)
Sound power level Cooling Nom. dBA 67.0 69.0 69.0
Dimensions Unit Width mm 1,380 1,380 1,380
    Depth mm 460 460 460
    Height mm 870 870 870
Capacity control Method   Variable (inverter) Variable (inverter) Variable (inverter)
Fan Air flow rate Cooling Nom. m³/min 70 85 85
Compressor Starting method   Inverter Inverter Inverter
Power supply Phase   3~ 3~ 3~
  Name   W1 W1 W1
  Frequency Hz 50 50 50
  Voltage V 400 400 400
Notes (1) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (1) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (1) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB
  (2) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (2) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (2) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB
  (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
  (4) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (4) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (4) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
  (5) - According to EN14825 (5) - According to EN14825 (5) - According to EN14825
  (6) - Depends on operation mode, refer to installation manual. (6) - Depends on operation mode, refer to installation manual. (6) - Depends on operation mode, refer to installation manual.
  (7) - For more details, see operation range drawing (7) - For more details, see operation range drawing (7) - For more details, see operation range drawing