ETBX16EF9W7 / EPRA14DAV37 |
ETBX16EF9W7 / EPRA16DAV37 |
ETBX16EF9W7 / EPRA18DAV37 |
Heating capacity
|
Min.
|
kW
|
3.70 (1)
|
3.96 (1)
|
4.40 (1)
|
|
Nom.
|
kW
|
5.69 (2)
|
9.00 (2)
|
9.00 (2)
|
|
Max.
|
kW
|
10.18 (1)
|
10.91 (1)
|
12.12 (1)
|
Cooling capacity
|
Nom.
|
kW
|
10.6 (3), 6.90 (4)
|
11.5 (3), 7.88 (4)
|
12.5 (3), 8.86 (4)
|
Power input
|
Heating
|
Min.
|
kW
|
0.88 (5)
|
0.95 (5)
|
1.05 (5)
|
|
|
Nom.
|
kW
|
1.22 (2)
|
1.80 (2)
|
1.80 (2)
|
|
|
Max.
|
kW
|
2.09 (5)
|
2.24 (5)
|
2.49 (5)
|
|
Cooling
|
Nom.
|
kW
|
2.55 (3), 2.56 (4)
|
2.80 (3), 2.93 (4)
|
3.05 (3), 3.31 (4)
|
COP
|
4.67 (2)
|
5.00 (2)
|
5.00 (2)
|
EER
|
4.13 (3), 2.70 (4)
|
4.11 (3), 2.69 (4)
|
4.09 (3), 2.68 (4)
|
Space heating
|
Average climate water outlet 55°C
|
General
|
SCOP
|
|
3.62
|
3.62
|
3.62
|
|
|
|
Seasonal space heating eff. class
|
|
A++
|
A++
|
A++
|
|
Average climate water outlet 35°C
|
General
|
SCOP
|
|
4.57
|
4.57
|
4.57
|
|
|
|
Seasonal space heating eff. class
|
|
A+++
|
A+++
|
A+++
|
Notes
|
(1) - Capacity according to standard EN14511 and valid for heated water range dT = 3~8°C at Ta 7°C
|
(1) - Capacity according to standard EN14511 and valid for heated water range dT = 3~8°C at Ta 7°C
|
(1) - Capacity according to standard EN14511 and valid for heated water range dT = 3~8°C at Ta 7°C
|
|
(2) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
|
(2) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
|
(2) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
|
|
(3) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB
|
(3) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB
|
(3) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB
|
|
(4) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB
|
(4) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB
|
(4) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB
|
|
(5) - Power input is total input of indoor and outdoor units, including the circulation pump; according to EN14511
|
(5) - Power input is total input of indoor and outdoor units, including the circulation pump; according to EN14511
|
(5) - Power input is total input of indoor and outdoor units, including the circulation pump; according to EN14511
|
|
(6) - Test at Ta DB/WB 7°C/6°C. According to EN 16147.
|
(6) - Test at Ta DB/WB 7°C/6°C. According to EN 16147.
|
(6) - Test at Ta DB/WB 7°C/6°C. According to EN 16147.
|
|
(7) - DB/WB 7°C/6°C - LWC 35°C (dT=5°C) with pump at full speed
|
(7) - DB/WB 7°C/6°C - LWC 35°C (dT=5°C) with pump at full speed
|
(7) - DB/WB 7°C/6°C - LWC 35°C (dT=5°C) with pump at full speed
|