ERSQ011AAV1 |
ERSQ014AAV1 |
ERSQ016AAV1 |
Sound pressure level
|
Heating
|
Nom.
|
dBA
|
52
|
53
|
55
|
Standard Accessories
|
Installation manual
|
1
|
1
|
1
|
Refrigerant
|
GWP
|
|
2,087.5
|
2,087.5
|
2,087.5
|
|
Charge
|
kg
|
4.5
|
4.5
|
4.5
|
|
Type
|
|
R-410A
|
R-410A
|
R-410A
|
Operation range
|
Heating
|
Max.
|
°CWB
|
20
|
20
|
20
|
|
|
Min.
|
°CWB
|
-20
|
-20
|
-20
|
|
Domestic hot water
|
Min.
|
°CDB
|
-20
|
-20
|
-20
|
|
|
Max.
|
°CDB
|
35
|
35
|
35
|
Piping connections
|
Heat insulation
|
|
Both liquid and gas pipes
|
Both liquid and gas pipes
|
Both liquid and gas pipes
|
|
Liquid
|
OD
|
mm
|
9.52
|
9.52
|
9.52
|
|
Gas
|
OD
|
mm
|
15.9
|
15.9
|
15.9
|
|
Drain
|
OD
|
mm
|
26x3
|
26x3
|
26x3
|
|
Level difference
|
IU - OU
|
Max.
|
m
|
30
|
30
|
30
|
Sound power level
|
Heating
|
Nom.
|
dBA
|
68
|
69
|
71
|
Dimensions
|
Unit
|
Width
|
mm
|
900
|
900
|
900
|
|
|
Depth
|
mm
|
320
|
320
|
320
|
|
|
Height
|
mm
|
1,345
|
1,345
|
1,345
|
Weight
|
Unit
|
kg
|
120
|
120
|
120
|
Power supply
|
Phase
|
|
1~
|
1~
|
1~
|
|
Name
|
|
V1
|
V1
|
V1
|
|
Frequency
|
Hz
|
50
|
50
|
50
|
|
Voltage
|
V
|
220-440
|
220-440
|
220-440
|
Current
|
Recommended fuses
|
A
|
25
|
25
|
25
|
Notes
|
(1) - See separate drawing for operation range
|
(1) - See separate drawing for operation range
|
(1) - See separate drawing for operation range
|
|
(2) - Zmax: In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (system impedance) ≤ Zmax
|
(2) - Zmax: In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (system impedance) ≤ Zmax
|
(2) - Zmax: In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (system impedance) ≤ Zmax
|
|
(3) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A
|
(3) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A
|
(3) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A
|
|
(4) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A
|
(4) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A
|
(4) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A
|
|
(5) - Contains fluorinated greenhouse gases
|
(5) - Contains fluorinated greenhouse gases
|
(5) - Contains fluorinated greenhouse gases
|