Specifications Table for BSV6Q-PV

BSV6Q100PV1
Standard Accessories Installation manual Installation manual
  Connection pipes Connection pipes
  Insulation pipe cover Insulation pipe cover
  Clamps Clamps
Maximum number of connectable indoor units per branch 6
Maximum number of connectable indoor units 36
Piping connections Outdoor unit Liquid Type   Brazing connection
      OD mm 15.9
    Discharge gas Type   Brazing connection
      OD mm 28.6
    Gas Type   Brazing connection
      OD mm 28.6
  Indoor unit Gas Type   Brazing connection
      OD mm 15.9
    Liquid OD mm 9.5
      Type   Brazing connection
Power input Cooling Nom. kW 0.030
  Heating Nom. kW 0.030
Maximum capacity index of connectable indoor units per branch 100
Dimensions Unit Width mm 1,577
    Depth mm 635
    Height mm 209
Weight Unit kg 89
Number of branches 6
Maximum capacity index of connectable indoor units 600
Power supply Phase   1~
  Frequency Hz 50
  Voltage V 220-240
  Name   V1
Notes (1) - In case of connection with a 20~50 type indoor unit, match to the size of the field pipe using the attached pipe. Connection between the attached pipe and the field pipe must be brazed.
  (2) - In case the joint diameter does not fit on the triple piping side, a reducer is needed (field supply)
  (3) - Insulators are necessary (field supply) for the triple piping side
  (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (5) - Maximum allowable voltage range variation between phases is 2%.
  (6) - MCA/MFA: MCA = 1.25 x FLA
  (7) - MFA ≤ 4 x FLA
  (8) - Next lower standard fuse rating minimum 15A
  (9) - Select wire size based on the value of MCA
  (10) - Instead of a fuse, use a circuit breaker