| BSV4Q100PV1 | |||||
|---|---|---|---|---|---|
| Standard Accessories | Installation manual | Installation manual | |||
| Attached piping | Attached piping | ||||
| Insulation pipe cover | Insulation pipe cover | ||||
| Clamps | Clamps | ||||
| Maximum number of connectable indoor units per branch | 6 | ||||
| Maximum number of connectable indoor units | 24 | ||||
| Piping connections | Outdoor unit | Liquid | Type | Brazing connection | |
| OD | mm | 12.7 | |||
| Discharge gas | Type | Brazing connection | |||
| OD | mm | 19.1 | |||
| Gas | Type | Brazing connection | |||
| OD | mm | 28.6 | |||
| Indoor unit | Gas | Type | Brazing connection | ||
| OD | mm | 15.9 | |||
| Liquid | OD | mm | 9.5 | ||
| Type | Brazing connection | ||||
| Power input | Cooling | Nom. | kW | 0.020 | |
| Heating | Nom. | kW | 0.020 | ||
| Maximum capacity index of connectable indoor units per branch | 100 | ||||
| Dimensions | Unit | Width | mm | 1,053 | |
| Depth | mm | 635 | |||
| Height | mm | 209 | |||
| Weight | Unit | kg | 60 | ||
| Number of branches | 4 | ||||
| Maximum capacity index of connectable indoor units | 400 | ||||
| Power supply | Phase | 1~ | |||
| Frequency | Hz | 50 | |||
| Voltage | V | 220-240 | |||
| Name | V1 | ||||
| Notes | (1) - In case of connection with a 20~50 type indoor unit, match to the size of the field pipe using the attached pipe. Connection between the attached pipe and the field pipe must be brazed. | ||||
| (2) - In case the joint diameter does not fit on the triple piping side, a reducer is needed (field supply) | |||||
| (3) - Insulators are necessary (field supply) for the triple piping side | |||||
| (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | |||||
| (5) - Maximum allowable voltage range variation between phases is 2%. | |||||
| (6) - MCA/MFA: MCA = 1.25 x FLA | |||||
| (7) - MFA ≤ 4 x FLA | |||||
| (8) - Next lower standard fuse rating minimum 15A | |||||
| (9) - Select wire size based on the value of MCA | |||||
| (10) - Instead of a fuse, use a circuit breaker | |||||