| 3AMXF52A2V1B9 | |||||
|---|---|---|---|---|---|
| Fan motor | Speed | Cooling | Super low | rpm | 420 |
| Heating | Super low | rpm | 420 | ||
| Compressor | Type | Hermetically sealed swing compressor | |||
| Operation range | Cooling | Ambient | Min. | °CDB | -10 |
| Max. | °CDB | 46 | |||
| Sound pressure level | Cooling | Nom. | dBA | 46 | |
| Heating | Nom. | dBA | 47.0 | ||
| Refrigerant | Charge | kg | 1.8 | ||
| Charge | tCO2Eq | 1.22 | |||
| Piping connections | Piping length | OU - IU | Max. | m | 25 (1) |
| Additional refrigerant charge | kg/m | 0.02 (for piping length exceeding 30m) | |||
| Level difference | IU - OU | Max. | m | 15.0 | |
| IU - IU | Max. | m | 7.5 | ||
| Total piping length | System | Actual | m | 50 | |
| Standard Accessories | Installation manual | 1 | |||
| Drain cap | 3 | ||||
| Drain plug | 1 | ||||
| Reducer assembly | 1 | ||||
| Screw bag | 1 | ||||
| Notes | (1) - For one room | ||||